Installation Manual Gear-Driven Centrifugal Water- Cooled Liquid Chillers Unit Model CVGF 400-1000 Ton Units (50 and 60 Hz) CVGF-SVN02B-E4 X39640686020...
Cut-out 165°F Cut-out 74°C Low oil temperature Cut-out 5°F below set point Cut-out 2.8°C below set point High motor temperature Cut-out 265°F ± 15°F Cut-out 130°C ± 8°C Oil Chart Europe Oil 0037 Oil 021E Oil 0049 Oil 0020E CVGF-SVN02B-E4...
Page 5
1500 VA MAX microcomputer-based control systems. A careful review of this WHEN MOTOR CONTROLLER PROVIDED BY OTHERS information along with the TRANE ENGINEERING SPEC. S6516-0360 APPLIES submittal package provided for GENERAL CHARACTERISTICS: the unit will assure that the REFRIGERANT SYSTEM chiller is correctly installed.
Page 6
Do not proceed with installation not occur after delivery. - Lists correct operating of a damaged unit without sales • Notify the Trane sales charges of HFC-134a and office approval. representative and arrange for lubrication oil repair. Do not repair the unit,...
Page 7
Each unit factory-charged with 15 gallons equipped with a unit-mounted is a completely assembled, (56.8L) of Trane Oil 37 and a starter. This includes the hermetic package that is factory- holding charge of 5 psig (34 kPa)
Page 8
Figure 2. Component location for typical CVGF unit Unit-mounted starter (optional) Two-stage compressor Condenser Relief valves Evaporator Oil Pump Control Panel CH530 Unit nameplate Figure 3. Component location for typical CVGF unit (back view) Motor Unit nameplate Relief valves Oil cooler Economizer CVGF-SVN02B-E4...
Page 10
49 Orifice series F = French 4 = .75 diameter .028 wall titanium 51 Orifice series G = German tube 56 Orifice series T = Italian S = Special SS = Special P = Spanish S = Special CVGF-SVN02B-E4...
Page 11
N = 15.1 Rim diameter C = (43rd digit) Control: Condenser S = Special Refrigerant Pressure 0 = None C = Condenser Refrigerant Pressure L = (44th digit) Manufacturing Location L = La Crosse, Wisconsin T = Tai Cang, China CVGF-SVN02B-E4...
Page 12
1 = (18th digit) Oil Pump Starter G = 40 KVAR H = 575V-60Hz-3Ph Circuit H = 45 KVAR R = 380V-50Hz-3Ph 1 = 1 HP Oil Pump Motor T = 400V-50Hz-3Ph 2 = 1.5 HP Oil Pump U = 415V-50Hz-3Ph S = Special CVGF-SVN02B-E4...
Page 13
1 = (18th digit) Oil Pump Starter H = 45 KVAR H = 575V-60Hz-3Ph Circuit R = 380V-50Hz-3Ph 1 = 1 HP Oil Pump Motor T = 400V-50Hz-3Ph 2 = 1.5 HP Oil Pump Motor U = 415V-50Hz-3Ph S = Special CVGF-SVN02B-E4...
Page 14
Flow switches (may be field-supplied) Water flow pressure gauges Isolation and balancing valves water piping Vent and drain valves Pressure relief valves (for water boxes as required) Pressure Relief Relief valves Vent line and flexible connector Insulation Insulation (optional) Insulation CVGF-SVN02B-E4...
Page 15
• Go over the pre-commissioning established. check sheet and ensure that all items have been completed. Note: reference graphs 1-16 in the Installation Mechanical • Start the unit under the section for proper water flow. supervision of a qualified service technician. CVGF-SVN02B-E4...
If the chiller is to be stored for at Noise Considerations over its length and width. least one month prior to • Locate the unit away from Trane is not responsible for installation, observe the sound-sensitive areas. equipment problems resulting following precautions: •...
Page 33
If the room configuration points. Refer to submittal requires a variance to the drawings for the unit clearance dimensions, contact dimensions. your Trane sales office Allow adequate clearance for representative. condenser and compressor servicing. A minimum of 36" (914 mm) is recommended for...
Page 34
CL1 at either end of the machine and is required for tube pull clearance. CL2 is always at the opposite end of the machine from CL1 and is required for service clearance. Add 14-5/8" (37.1 cm) on each end for the water box. CVGF-SVN02B-E4...
Page 35
CL1 at either end of the machine and is required for tube pull clearance. CL2 is always at the opposite end of the machine from CL1 and is required for service clearance. Add 14-5/8" (37.1 cm) on each end for the water box. CVGF-SVN02B-E4...
Page 36
(0°C). serious injury. See details below: • Follow the procedures and diagrams in this manual and in the submittal. • Always use lifting equipment with a capacity exceeding the unit lifting weight by an adequate safety factor. (+10%). CVGF-SVN02B-E4...
Page 37
3. If required, bolt the isolators Figure 7 and Figure 8. necessary, contact your local to the floor through the slots Trane sales office for further Note: Three types of spring provided, or cement the pads. information. isolators, shown in Tables 11-13 Note: fastening the isolators are used.
Page 38
Remember that the chiller must be level to within 1/4" (6 mm) over its length and width and that clearance of each isolator must be 1/4" (6 mm). CVGF-SVN02B-E4...
Page 39
10 UNC Adjusting and leveling bolt Adjust isolator so that the upper housing clears the lower housing by at least 1/4" (6.3mm) and not more than 1/2" (12.7mm) Free Height 1/4" (6.3mm) Acoustical nonskid neoprene pad (top and bottom) CVGF-SVN02B-E4...
Page 40
9431 (4278) 12665 (5745) 6090 (2762) 8991 (4078) 11500 (5216) 7225 (3277) 10340 (4690) 13545 (6144) Table 11. Selected spring isolators – CVGF 500 Trane Part Maximum Load Location Isolator type Spring Color Deflection lbm (kg) Used and size Coding...
Page 41
Anchor Bolt Detail Nuts should not be tight. Unit mounting pad 13 mm Leave 2 to 3 mm gap. thick (by Trane) Vibration isolator (by Trane) Anchor Hole Detail 75 mm steel pipe 4 × 22 mm Evaporator diameter holes for...
Page 42
2 pass waterboxes Flow (in GPM) Bundle C Bundle A Bundle B Graph 2. Pressure drop for CVGF 500 Condensers with 0.75 inch OD tubes and 2 pass waterboxes Flow (in GPM) Bundle C Bundle A Bundle B CVGF-SVN02B-E4...
Page 43
2 pass waterboxes Flow (in GPM) Bundle C Bundle A Bundle B Graph 4. Pressure drop for CVGF 500 Condensers with 1.0 inch OD tubes and 2 pass waterboxes Flow (in GPM) Bundle C Bundle A Bundle B CVGF-SVN02B-E4...
Page 44
2 pass waterboxes Flow (in GPM) Bundle C Bundle A Bundle B Graph 6. Pressure drop for CVGF 700 Condensers with 3/4 inch OD tubes and 2 pass waterboxes Flow (in GPM) Bundle A Bundle B Bundle C CVGF-SVN02B-E4...
Page 45
3 pass waterboxes Flow (in GPM) Bundle C Bundle A Bundle B Graph 8. Pressure drop for CVGF 700 Evaporators with 1.0 inch OD tubes and 2 pass waterboxes Flow (in GPM) Bundle A Bundle C Bundle B CVGF-SVN02B-E4...
Page 46
2 pass waterboxes Flow (in GPM) Bundle A Bundle C Bundle B Graph 10. Pressure drop for CVGF 700 Evaporators with 1.0 inch OD tubes and 3 pass waterboxes Flow (in GPM) Bundle A Bundle C Bundle B CVGF-SVN02B-E4...
Page 47
Flow (in GPM) Bundle A Bundle B Bundle C Bundle D Graph 12. Pressure drop for CVGF 1000 Evaporators with 3/4 inch OD tubes and 3 pass waterboxes Flow (in GPM) Bundle A Bundle B Bundle D Bundle C CVGF-SVN02B-E4...
Page 48
Flow (in GPM) Bundle A Bundle B Bundle C Bundle D Graph 14. Pressure drop for CVGF 1000 Evaporators with 1.0 inch OD tubes and 2 pass waterboxes Flow (in GPM) Bundle A Bundle B Bundle C Bundle D CVGF-SVN02B-E4...
Page 49
Flow (in GPM) Bundle A Bundle B Bundle C Bundle D Graph 16. Pressure drop for CVGF 1000 Evaporators with 1.0 inch OD tubes and 3 pass waterboxes Flow (in GPM) Bundle A Bundle B Bundle C Bundle D CVGF-SVN02B-E4...
Page 50
To drain water, remove the vent and drain plugs or open the ball valves. Install an NPT connectors in the drain connection, and connect a hose to it. CVGF-SVN02B-E4...
The safety. These components and what treatment, if any, is maximum pressure for high- their general locations are given advisable. The Trane Company pressure water boxes is 300 psig below. warranty specifically excludes (2100 kPa). liability for corrosion, erosion, or...
Page 52
This coupled shutoff valves have a eliminates errors resulting from high potential for hydrostatic differently calibrated gauges pressure buildup during a water installed at unmatched temperature increase. Refer to elevations. applicable codes for pressure- relief valve installation guidelines. CVGF-SVN02B-E4...
Page 53
If machine below. shutdowns persist, contact your • Mount the switch upright, with local Trane representative. a minimum of 5 pipe diameters • Adjust the switch to open when of straight, horizontal run on water flow falls below nominal.
Page 54
Note: Relief valves tend to leak if Standard 15 for vent pipe sizing. with higher humidity may they have opened and must be All country, federal, state, and require additional insulation. replaced. local codes take precedence over any suggestions stated in this manual. CVGF-SVN02B-E4...
Page 55
(Square m) Evaporator, waterboxes and tube sheets 3/4" wall (19 mm) 160 (15) 3/4" wall (19 mm) 20 (2) Compressor suction elbow and suction cover All components and piping on low side of system 3/4" wall (19 mm) 10 (1) CVGF-SVN02B-E4...
CAUTION TO AVOID DAMAGE TO STARTER COMPONENTS, remove debris inside the starter panel. Failure to do so may cause an electrical short that seriously damages the starter components. CVGF-SVN02B-E4...
Page 57
See Figure 14. To avoid damage remove debris inside the starter panel. Failure to do so may cause an electrical short that seriously damages the starter components. Figure 14. Proper phasing for starter power supply wiring and conduit loading CVGF-SVN02B-E4...
Page 58
Figure 15. PFCC leads routed through overload current transformer cause motor damage. Line Line PFCC PFCC Overload Overload Current Current - OR - Transformer Transformer Load Motor Load Motor Note: See the attached wiring diagram for more detail. CVGF-SVN02B-E4...
Page 59
Figure 16. Typical equipment room layout with unit-mounted, Wye- Delta Line Side Power Conduits Unit Control Unit Mounted Panel Starter Note: See Starter submittal drawing for location of incoming wiring to the starter. CVGF-SVN02B-E4...
Page 60
2. 115-volt conduit must enter the higher than 30 Vdc Class I portion of the unit control panel. 3. IPC circuit conduit must enter the Low Voltage Class II portion of the UCP. 4. See starter submittal drawing for location of incoming wiring to the starter. CVGF-SVN02B-E4...
Page 61
(These connections will be Wire Terminal Lugs completed under supervision Note: Install control voltage Wire terminal lugs must be field- of a qualified Trane service conduit into control voltage supplied. engineer after the prestart section of chiller control panel 1. Use field-provided crimp-type inspection).
Page 62
Beldon Type 8760, 18 AWG to the UCP at Terminals 1A-J2- for runs up to 1000 feet. 7 and 1A9-J2-9. Note: The polarity of the IPC wire pair is critical for proper operation. CVGF-SVN02B-E4...
Page 63
Installation: Electrical Figure 18. Terminal stud, clamp and lug assembly Belleville washer Terminal lugs 3/8"* Bolt Belleville washer Motor terminal Terminal stud clamp Front View Mid Voltage RXL RATR RPIR CXL CATR CPIR CVGF-SVN02B-E4...
Page 64
It is recommended that the operator instruction. Communication Interface serviceman contact the local Trane office to obtain the most Advance notification is required This control options allows the to assure that initial start-up is recent printing date of the form.
Page 65
Multiple Sites Modem Building Control Unit Chilled Water Chilled Water Supply (CHW) Supply (CHW) and Return and Return Condenser Condenser Water Chilled Water Water Pump Chilled Water Temperature Water Temperature Water Pump Sensors Chiller 1 Pump Sensors Chiller 2 Pump CVGF-SVN02B-E4...
Page 68
A business of American Standard Companies www.trane.com Société Trane – Société Anonyme au capital de 41500 000 F – Siege Social: 1 rue des Amériques – 88190 Golbey – France – Siret 306 050 188-00011 – RSC Epinal B 306 050 188 For more information contact your local Trane office Numéro d’identification taxe intracommunanutaire: FR 83 3060501888...