Electrical Testing Of Connections; Testing And Addressing The Ethernet/Ip Connection; Configuration - Allen-Bradley 1719 Ex I/O User Manual

Table of Contents

Advertisement

Electrical Testing of
Connections

Configuration

Commissioning
Topic

Electrical Testing of Connections

Configuration
Startup Phase
Make sure that the plugs have been properly fitted to the EtherNet/IP RJ45
ports.
For more information, see EtherNet/IP Connection section of the 1719 Ex I/O
Installation Instructions, publication 1719-IN001.

Testing and Addressing the EtherNet/IP Connection

WARNING: Risk of explosion
When taking measurements in hazardous areas, there is a risk of explosion from
sparks forming.
Take measurements on the terminal connections of a distributed I/O station, with a
hot work permit only, in other words when there is no potentially explosive
atmosphere.
For information about testing and addressing of EtherNet/IP modules, refer to
the EtherNet/IP Adapter User Manual, publication ENET-UM001.
If you have not installed the Rockwell Software® BOOTP-DHCP Server for
setting the network IP address, you can download and install it from:
http://www.software.rockwell.com/download/comms/rsnetworx/bootp-
dhcp%20server%202.3.2.zip.
The entire distributed I/O station is configured in the Add-on Profile:
1. Add a network card to the project (if needed).
2. Add a 1719 adapter to the project. Enable the status connection if
diagnostics are needed.