  • Page 1: Table Of Contents

    Installation Instructions FLEX I/O Digital Input and Output Modules with Diagnostics Catalog numbers 1794-IB16D, 1794-OB16D Table of Contents Topic Page Important User Information Environment and Enclosure Preventing Electrostatic Discharge North American Hazardous Location Approval Install the Isolated Analog Output Module...
  • Page 2: Important User Information

    2 FLEX I/O Digital Input and Output Modules with Diagnostics Important User Information Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation, and Maintenance of Solid-State Controls (Publication SGI-1.1 available from your local Rockwell Automation Sales Office or online at http://www.rockwellautomation.com/literature/) describes some important differences between solid-state equipment and hard-wired electromechanical devices.
  • Page 3: Environment And Enclosure

    FLEX I/O Digital Input and Output Modules with Diagnostics Environment and Enclosure ATTENTION: This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in EN/IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating. This equipment is not intended for use in residential environments and may not provide adequate protection to radio communication services in such environments.
  • Page 4 4 FLEX I/O Digital Input and Output Modules with Diagnostics ATTENTION: This product is grounded through the DIN rail to chassis ground. Use zinc plated chromate-passivated steel DIN rail to assure proper grounding. The use of other DIN rail materials (for example, aluminum or plastic) that can corrode, oxidize, or are poor conductors, can result in improper or intermittent grounding.
  • Page 5 FLEX I/O Digital Input and Output Modules with Diagnostics WARNING: When you insert or remove the module while backplane power is on, an electric arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
  • Page 6: North American Hazardous Location Approval

    6 FLEX I/O Digital Input and Output Modules with Diagnostics North American Hazardous Location Approval The following modules are North American Hazardous Location approved: 1794-IB16D, 1794-OB16D. The following information applies when Informations sur l’utilisation de cet équipement operating this equipment in hazardous...
  • Page 7: Install The Isolated Analog Output Module

    FLEX I/O Digital Input and Output Modules with Diagnostics Install the Isolated Analog Output Module 45284 Component Identification Description Description Flexbus connectors Groove Latching mechanism Alignment bar Keyswitch Module Terminal base The input module mounts on a 1794-TB32 or 1794-TB32S terminal base. The output module mounts on a 1794-TB2, 1794-TB3, or 1794-TB3S terminal base.
  • Page 8 8 FLEX I/O Digital Input and Output Modules with Diagnostics 1794-TB32 and 1794-TB32S Terminal Base Wiring for 1794-IB16D Input Terminals 0…15 Sensor Power Terminals 0…15 +V1 COM1 +V1 COM1 +V1 COM1 +V1 COM1 +V2 COM2 +V2 COM2 +V2 COM2 +V2 COM2 NC...
  • Page 9 FLEX I/O Digital Input and Output Modules with Diagnostics ATTENTION: Do not remove or replace a Terminal Base unit while power is applied. Interruption of the backplane can result in unintentional operation or machine motion. Connecting Wiring for the 1794-OB16D Module use with 1794-TB2, 1794-TB3, or 1794-TB3S Terminal Base Connect individual output wiring to numbered terminals on the 0-15 row (A) as indicated in the Wiring Connections for 1794-OB16D table.
  • Page 10 10 FLEX I/O Digital Input and Output Modules with Diagnostics Wiring Connections for the 1794-OB16D Output Module use with 1794-TB2, 1794-TB3, or 1794-TB3S terminal base Output Output Terminal Common Terminal Output 00 B-17 Output 01 B-18 Output 02 B-19 Output 03 B-20 Output 04 B-21...
  • Page 11: Diagnostics

    FLEX I/O Digital Input and Output Modules with Diagnostics Diagnostics See configuration information below for location of diagnostic bits. Note: Each unused sensor port requires a dummy resistor to mask the channel diagnostic function. Diagnostic Functions for the 1794-IB16D Ext. Wiring Input Channel...
  • Page 12: Publication 1794-In096D-En-P - June

    12 FLEX I/O Digital Input and Output Modules with Diagnostics Diagnostic Functions for the 1794-OB16D Ext. Wiring Input Channel Open Short Rev. Module Power Status Wire Error Bit Error Bit Error Status Error Bit Bit/LED Open 0/OFF 0/OFF Short 0/OFF 0/OFF Normal 0/OFF...
  • Page 13 FLEX I/O Digital Input and Output Modules with Diagnostics Sensor Diagram for the 1794-IB16D Module External External External External 1794-IB16D 1794-IB16D 1794-IB16D 1794-IB16D Power Power Power Power Supply Supply Supply Supply 2-Wire 2-Wire 3-Wire 3-Wire Sensor Sensor Sensor Sensor 2-Wire...
  • Page 14: Configuration

    Remote I/O network with 1794-ASB series E or later, DeviceNet network, and the ControlNet network. Note: You must use the Module Connection when used in a ControlNet system Image Table Memory Map for the 1794-IB16D Module Read 1 Read 2...
  • Page 15 To set the input filter time, set the associated bits in the output image (complementary word) for the module. Dec. 14 13 11 10 O:010 1794-IB16D FT = 0-15 Write filter time on system startup. Write FT to complement of input module. I:000...
  • Page 16: Specifications

    Bit 01 = External power reverse polarity error; Bit 02 = Output short error; Bit 03 = Output open wire error Specifications Specifications – 16 Input Module w/ Diagnostics, 1794-IB16D Meets IEC 3 24V DC input specifications Attribute Value Number of inputs...
  • Page 17 FLEX I/O Digital Input and Output Modules with Diagnostics Specifications – 16 Input Module w/ Diagnostics, 1794-IB16D Meets IEC 3 24V DC input specifications Attribute Value Flexbus current 30 mA @ 5V DC Power dissipation, max 8.5 W @ 31.2V DC Thermal dissipation, max 29 BTU/hr @ 31.2V DC...
  • Page 18 Determined by installed terminal base Dimensions, approx. (H x W x D) 45.7 x 94 x 53.3 mm (1.8 x 3.7 x 2.1 in.) – 1794-IB16D 94 x 94 x 91 mm (3.7 x 3.7 x 3.6 in.) – 1794-OB16D Weight, approx.
  • Page 19 FLEX I/O Digital Input and Output Modules with Diagnostics Environmental Specifications Attribute Value Operating temperature IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock): 0 °C < Ta < +55 °C (+32 °F < Ta < +131 °F) Temperature, surrounding air, 55 °C (131 °F) max.
  • Page 20 20 FLEX I/O Digital Input and Output Modules with Diagnostics Certifications Certifications (when Value product is marked) c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E322657. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S.
  • Page 21 FLEX I/O Digital Input and Output Modules with Diagnostics Derating Curves 1794-IB16D Input Voltage 31 .2 26 .4 Input Voltage 50 55 Ambient Temperature (˚C) Sensor Power Sensor Power Current (m A ) 50 55 Ambient Temperature (˚C) WARNING: When used in a Class I, Division 2, hazardous location, this equipment must be mounted in a suitable enclosure with proper wiring method that complies with the governing electrical codes.
  • Page 22 22 FLEX I/O Digital Input and Output Modules with Diagnostics Notes: Publication 1794-IN096D-EN-P - June 2018...
  • Page 23 FLEX I/O Digital Input and Output Modules with Diagnostics Notes: Publication 1794-IN096D-EN-P - June 2018...
  • Page 24 RA-DU002, available at http://www.rockwellautomation.com/literature/. Allen-Bradley, Rockwell Automation, FLEX I/O, Rockwell Software, and TechConnect are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies. Publication 1794-IN096D-EN-P - June 2018 Supersedes Publication 1794-IN096C-EN-P - August 2015 Copyright ©...