SMA Solar Technology AG
Parameter
Start setpoint active power limita-
tion
End setpoint active power limita-
tion
For reactive power setpoint in %:
Start setpoint reactive power
For reactive power setpoint in %:
End setpoint reactive power
For setpoint cos Phi:
Cos Phi start setpoint
For setpoint cos Phi:
Cos Phi end setpoint
For setpoint cos Phi:
Excitation type
Example of the importance of lower and upper limits for setpoints
4 mA is set as the initial value for the active power limitation setpoint and 16 mA is set as the end
value for the active power limitation setpoint. If the grid operator sends a signal of 3.5 mA to the
Cluster Controller, the Cluster Controller then classifies this signal as 4 mA because the value of
4 mA is set as the lower limit for the active power limitation setpoint. If the grid operator sends a
signal of 17 mA to the Cluster Controller, the Cluster Controller then classifies this signal as 16 mA
because the value of 16 mA is set as the upper limit for the active power limitation setpoint.
User Manual
Explanation
Lower limit for the setpoint for the active power limitation re-
lated to the inverter parameter Set active power limit or
Pmax
Upper limit for the setpoint for the active power limitation re-
lated to the inverter parameter Set active power limit or
Pmax
Lower limit for the setpoint for the reactive power setpoint re-
lated to the inverter parameter Set active power limit or
Pmax
Upper limit for the setpoint for the reactive power setpoint re-
lated to the inverter parameter Set active power limit or
Pmax
Lower limit for the setpoint of the displacement power factor
cos φ
Upper limit for the setpoint of the displacement power factor
cos φ
Direction of phase shift
4 User Interface of the Cluster Controller
ClusterController-BA-en-15