Emerson Unidrive M201 Installation Manual page 33

Unidrive hs series; unidrive m series. frame 7 to 10
Hide thumbs Also See for Unidrive M201:
Table of Contents

Advertisement

Where:
V
Air-flow in m
Maximum expected temperature in °C outside the enclosure
T
ext
T
Maximum permissible temperature in °C inside the enclosure
int
P
Power in Watts dissipated by all heat sources in the enclosure
P
------ -
k
Ratio of
P
Where:
P
is the air pressure at sea level
0
P
is the air pressure at the installation
I
Typically use a factor of 1.2 to 1.3, to allow also for pressure-drops in dirty air-filters.
Example
To calculate the size of an enclosure for the following:
Three drives operating at the Normal Duty rating
External EMC filter for each drive
Braking resistors are to be mounted outside the enclosure
Maximum ambient temperature inside the enclosure: 40 °C
Maximum ambient temperature outside the enclosure: 30 °C
For example, dissipation of each drive: 101 W and dissipation of each external EMC filter: 6.9 W
(max).
Total dissipation: 3 x (101 + 6.9) = 323.7 W
Insert the following values:
40 °C
T
int
T
30 °C
ext
k
1.3
P
323.7 W
Then:
×
×
3
1.3
V
=
-------------------------------------- -
40 30
3
= 126.2 m
/hr (74.5 ft
Unidrive M / HS Frame 7 to 10 Power Installation Guide
Issue Number: 5
3
3
per hour (1 m
/hr = 0.59 ft
o
l
323.7
3
3
/min) (1 m
/ hr = 0.59 ft
3
/min)
3
/min)
33