Emerson Unidrive M201 Installation Manual page 103

Unidrive hs series; unidrive m series. frame 7 to 10
Hide thumbs Also See for Unidrive M201:
Table of Contents

Advertisement

5.1.20
Input current, fuse and cable size ratings
The input current is affected by the supply voltage and impedance.
Typical input current
The values of typical input current are given to aid calculations for power flow and power loss.
The values of typical input current are stated for a balanced supply.
Maximum continuous input current
The values of maximum continuous input current are given to aid the selection of cables and fuses.
These values are stated for the worst case condition with the unusual combination of stiff supply with
bad balance. The value stated for the maximum continuous input current would only be seen in one
of the input phases. The current in the other two phases would be significantly lower.
The values of maximum input current are stated for a supply with a 2 % negative phase-sequence
imbalance and rated at the maximum supply fault current of 100kA.
Table 5-15 AC Input current and fuse ratings (200 V)
Maximum
Typical
continuous
input
Model
current
A
07200610
58
07200750
73
07200830
91
08201160
123
08201320
149
09201760
172
09202190
228
10202830
277
10203000
333
Table 5-16 AC Input current and fuse ratings (400 V)
Maximum
Typical
continuous
input
Model
current
A
07400660
67
07400770
80
07401000
96
08401340
137
08401570
164
09402000
211
09402240
245
10402700
306
10403200
370
* These fuses are fast acting.
Unidrive M / HS Frame 7 to 10 Power Installation Guide
Issue Number: 5
Maximum
overload
input
input
current
current
A
A
67
109
84
135
105
149
137
213
166
243
205
270
260
319
305
421
361
494
Maximum
overload
input
input
current
current
A
A
74
124
88
145
105
188
155
267
177
303
232
306
267
359
332
445
397
523
Fuse rating
IEC
Nominal
Max
Class
A
A
80
80
100
100
gG
125
125
200
200
gR
250
250
gR
315
315
400
400
gR
450
450
Fuse rating
IEC
Nominal
Max
Class
A
A
100
100
gG
125
125
250
250
gR
315
315
gR
400
400
gR
450
450
UL / USA
Nominal
Max
Class
A
A
80
80
100
100
CC, J or T*
125
125
200
200
HSJ
225
225
250
250
HSJ
300
300
400
400
HSJ
450
450
UL / USA
Nominal
Max
Class
A
A
80
80
100
100
CC, J or T*
125
125
225
225
HSJ
300
300
HSJ
350
350
400
400
HSJ
450
450
103