Emerson Unidrive M201 Installation Manual page 113

Unidrive hs series; unidrive m series. frame 7 to 10
Hide thumbs Also See for Unidrive M201:
Table of Contents

Advertisement

Key (shown in decreasing order of permitted emission level):
E2R
EN 61800-3 second environment, restricted distribution (Additional measures may be
required to prevent interference)
E2U
EN 61800-3 second environment, unrestricted distribution
I
Industrial generic standard EN 61000-6-4
EN 61800-3 first environment restricted distribution (The following caution is required by EN
61800-3)
This is a product of the restricted distribution class according to IEC 61800-3. In a
residential environment this product may cause radio interference in which case the user
may be required to take adequate measures.
CAUTION
R
Residential generic standard EN 61000-6-3
EN 61800-3 first environment unrestricted distribution
EN 61800-3 defines the following:
The first environment is one that includes residential premises. It also includes establishments
directly connected without intermediate transformers to a low-voltage power supply network
which supplies buildings used for residential purposes.
The second environment is one that includes all establishments other than those directly
connected to a low-voltage power supply network which supplies buildings used for residential
purposes.
Restricted distribution is defined as a mode of sales distribution in which the manufacturer
restricts the supply of equipment to suppliers, customers or users who separately or jointly have
technical competence in the EMC requirements of the application of drives.
EN 61800-3:2004+A1:2012
The 2004 revision of the standard uses different terminology to align the requirements of the
standard better with the EC EMC Directive.
Power drive systems are categorized C1 to C4:
Category
C1
Intended for use in the first or second environments
Not a plug-in or movable device, and intended for use in
C2
the first environment only when installed by a
professional, or in the second environment
Intended for use in the second environment, not the first
C3
environment
Intended for use in the second environment in a system
C4
rated at over 400 A or in a complex system
Note that category 4 is more restrictive than E2R, since the rated current of the PDS must exceed
400 A or the supply voltage exceed 1000 V, for the complete PDS.
Unidrive M / HS Frame 7 to 10 Power Installation Guide
Issue Number: 5
Definition
Corresponding code
used previously
R
I
E2U
E2R
113