Setup wizard via MMIGRS2 display
When all connections to the controller have been made, after the power is switched on, the Danfoss logo will appear
for 5 seconds, then the Home screen will be displayed.
To access the Wizard: press and hold enter to access the Login screen, the commissioning password is 300, scroll down
the Setup and service menu and select "Setup wizard".
The Wizard workflow is: a. Language selection; b. Application selection; c. Input configuration; and d.
Output configuration.
When using the Setup Wizard, repeat the following sequence for all parameter settings:
a. From Setup wizard, select relevant parameters.
b. Press ENTER to highlight 1st option
c. Scroll with UP / DOWN to your desired option
d. If the selected default value is acceptable, press DOWN to get to the next settings. Otherwise,
press ENTER to set your choice
e. Scroll with DOWN to the next parameter (repeat sequence a. to e.)
Note:
• If you do not have sufficient information to complete the Wizard, leave settings on their default values. To generate
the requested info, you can use Danfoss Coolselector2 software to calculate operating conditions and valve OD for the
same operating point.
• Setup Wizard only covers the most important parameters. If other features are to be enabled
(e.g. Alarm settings, MOP/LOP, etc.), they must be configured separately once the Setup Wizard is done.
Setup Wizard is also available in KoolProg PC tool.
The workflow process is the same as that described above for MMIGRS2 display.
For details, please refer to EKE data sheet.

Status menu

QR code
Controller info
Detailed status
SH trend 25 min
Display
© Danfoss | DCS (az) | 2018.06
1
1
Power on
3
3
2
2
Commissioning 300
Service 200
Daily 100
Press and
hold enter
Home menu
Danfoss
Danfoss
80G294.20
80G294.20
Login
PW:
5
5
Esc
Setup and service
Reference
Control
Defrost
Alarm configuration
IO config
Display
Communication
Service
Setup wizard
Controller name