Quick guide for parameter selection
Apart from wizard setup, users can also use the following section which describes quick parameter
settings for general applications.
Driver
Start : Main switch= Off
Select valve type
Application mode
Driver- Controller
Analog signal type
e.g 1- 5V / 0 - 10V.
Parameter I033 Driver
reference configuration,
I034 Ext ref voltage low,
I035 Ext ref. voltage high
© Danfoss | DCS (az) | 2018.06
Controller
Select Refrigerant
Select Temperature sensor
Select Pressure transmitter
Define Min/Max Pressure
Select Superheat Control
Set Min/Max Ref value
Select Other features
Finish: main switch = ON
Make sure that main switch is OFF before changing
the settings. The setting will depend on the system
requirement.
Parameter: R012 Main Switch
Select predefined Danfoss valve type ETS, ETS C, KVS,
KVS C, CCM, CCMT, CTR, or user defined.
Parameter: I067 Valve configuration
Select how you want to use EKE: driver or superheat
controller.
Parameter: R102 Operation mode
Select the predefined refrigerant
Parameter: O030 Refrigerant
Select Temperature sensor type: EKS, ACCPBT, MBT,
Sensata 112CP, Bus shared
Parameter: I081 - S2 sensor configuration.
Check parameter list for other sensors.
Select Pressure transmitter type –AKS 32R, Sensata
112CP, OEM Ratio, NSK, AKS 32 1 - 5 V,
OEM Voltage, Bus shared
Parameter: I085 - Pe transmitter configuration.
Check parameter list for other sensors.
Define min and max Pressure transmitter in barg.
Parameter: O020 - Pe min., O021 Pe max., Check
parameter list for other sensors.
Select application control type SH control. 1: MSS,
2: LoadAp, 3: Fixed, 4: Delta SH.
Parameter: N021 SH reference mode.
Set the value for the selected control min./max.
superheat reference.
Parameter N009 SH max., N010 - SH min.
Optional – Force start up, MOP, LOP, Alarm,
Thermostat function.
Check parameter list for details.
Remember to turn on main switch to start 'ON' .
Parameter R012 Main switch.
.
DKRCC.PI.RS0.C6.02 | 12