Sensor mounting: Temperature sensor
1
Conductive
paste
Important Note
• Mount the sensor on a clean
paint-free surface.
• Remember to use heat
conducting paste and insulate
the sensor.
For precise measurements,
mount the sensor max. 5 cm
from the outlet of the evaporator.
Pressure transmitter
• Installation of the pressure transmitter is less critical. However, the pressure transmitter should be closer to
the temperature sensor, right after the evaporator and with its head upright. It is a good practice to select
a pressure transmitter with an average load of 40 - 60% of full scale.
• 5 EKEs at maximum are allowed to share the output signal of a ratiometric pressure transmitter.
In order to get a correct acquisition on all the units all the three wires (GND, 5 V and transmitter signal
output) must be routed to every unit.
Power supply
• Power sharing is allowed in EKE controller.
• It is a good practice not to reverse the polarity of the power connection cables.
Selection of the common power supply depends on the total number of sharings and the valve in use.
Power supply
© Danfoss | DCS (az) | 2018.06
2
Evaporator outlet
D f
Danfoss
84N403.10
EKE
CAN RJ
CAN RJ
Superheat controller
Superheat controller
EKE 1x - 080G5xxx
3
OD
OD
OD
OD
Close to the
Close to the
Evaporator
evaporator
evaporator
EKE
CAN RJ
CAN RJ
Superheat controller
Superheat controller
EKE 1x - 080G5xxx
/
-
/
in.
1
5
2
8
12 - 16 mm
/
-
/
in.
3
7
4
8
18 - 22 mm
1 - 1
/
in.
3
8
25 - 35 mm
1
/
in. and higher
3
8
35 mm and higher
EKE
CAN RJ
CAN RJ
Superheat controller
Superheat controller
EKE 1x - 080G5xxx
DKRCC.PI.RS0.C6.02 | 6