Clearances To Combustibles - Quadra-Fire 3100-I Installation Manual

Wood insert automatic combustion control, acc
Table of Contents

Advertisement

B. Clearances to Combustibles
32-1/4 in
(819mm)
USA 16-3/4 in (171mm)
CANADA
24-3/4 in (629mm)
If trim measurement is over 3/4 in (19mm)
NOTE:
in depth use mantle or side clearances to
combustibles.
Without Mantel Deflector
51 7/16
1306mm
See next page for thermal protection
In Canada a full length 6 inch (152mm) S635 flue liner required as per ULC S628.
In USA a minimum 5 ft length (1.82m), 6 inch (152mm) diameter flue liner is required as per UL 1482.
WARNING
Fire Risk.
Comply with all minimum clearances to
combustibles as specified.
Failure to comply may cause house fire.
August 13, 2018
TOP TRIM
27-1/4 in
(692mm)
HEARTH
EXTENSION
12in max
MANTEL
USA 23-1/2
CANADA 25-1/2 (648mm)
HEARTH EXTENSION
calculations
United States and Canada (UL and ULC)
40-11/16 in
(1033mm)
Minimum Opening Dimensions
A
Height
B
Front Width
C
Back Width
D
Depth
NOTE: Minimum opening dimensions include a 1/4"
(6mm) clearance around unit.
41 7/16
1052mm
NOTE: Clearances may only be reduced by means
approved by the regulatory authority having
jurisdiction
7044-225I
3100 Insert ACC
A
D
C
B
Inches
22-3/4
28-7/8
24-1/8
14-1/2
With Mantel Deflector
12in max
MANTEL
USA 23-1/2
CANADA 25-1/2 (648mm)
Optional
Mantel
Deflector
HEARTH EXTENSION
See next page for thermal protection
calculations
Millimeters
578
733
613
368
9