B. Clearances to Combustibles
32-1/4 in
(819mm)
USA 16-3/4 in (171mm)
CANADA
24-3/4 in (629mm)
If trim measurement is over 3/4 in (19mm)
NOTE:
in depth use mantle or side clearances to
combustibles.
Without Mantel Deflector
51 7/16
1306mm
See next page for thermal protection
In Canada a full length 6 inch (152mm) S635 flue liner required as per ULC S628.
In USA a minimum 5 ft length (1.82m), 6 inch (152mm) diameter flue liner is required as per UL 1482.
WARNING
Fire Risk.
•
Comply with all minimum clearances to
combustibles as specified.
•
Failure to comply may cause house fire.
August 13, 2018
TOP TRIM
27-1/4 in
(692mm)
HEARTH
EXTENSION
12in max
MANTEL
USA 23-1/2
CANADA 25-1/2 (648mm)
HEARTH EXTENSION
calculations
United States and Canada (UL and ULC)
40-11/16 in
(1033mm)
Minimum Opening Dimensions
A
Height
B
Front Width
C
Back Width
D
Depth
NOTE: Minimum opening dimensions include a 1/4"
(6mm) clearance around unit.
41 7/16
1052mm
NOTE: Clearances may only be reduced by means
approved by the regulatory authority having
jurisdiction
7044-225I
3100 Insert ACC
A
D
C
B
Inches
22-3/4
28-7/8
24-1/8
14-1/2
With Mantel Deflector
12in max
MANTEL
USA 23-1/2
CANADA 25-1/2 (648mm)
Optional
Mantel
Deflector
HEARTH EXTENSION
See next page for thermal protection
calculations
Millimeters
578
733
613
368
9