Control unit
On the front of the frequency converter there is a
control panel.
The control panel is divided into four function groups:
1. Six-digit LED display.
2. Keys for changing parameters and shifting display
function.
3. Indicator lamps.
4. Keys for local operation.
All displays of data are in the form of a six-digit LED
display capable of showing one item of operating
data continuously during normal operation. As a
supplement to the display, there are three indicator
lamps for indication of mains connection (ON), warn-
ing (WARNING) and alarm (ALARM). Most of the
frequency converter's parameter Setups can be
changed immediately via the control panel, unless
this function has been programmed as Locked [1]
via parameter 018 Lock for data changes.
Control keys
[QUICK MENU] allows access to the parameters
used for the Quick menu.
The[QUICK MENU] key is also used if a change to a
parameter value is not to be implemented.
See also [QUICK MENU] + [+].
[CHANGE DATA] is used for changing a setting.
The [CHANGE DATA] key is also used for confirming
a change of parameter settings.
MG.28.A5.02 - VLT is a registered Danfoss trade mark
®
VLT
2800 Series
[+] / [-] are used for selecting parameters and for
changing parameter values.
These keys are also used in Display mode for se-
lecting the display of an operating value.
The [QUICK MENU] + [+] keys must be pressed at
the same time to give access to all parameters. See
Menu mode.
[STOP/RESET] is used for stopping the connected
motor or for resetting the frequency converter after a
trip.
Can be selected as Active [1] or Not active [0] via
parameter 014 Local stop/reset. In Display mode,
the display will flash if the stop function is activated.
NB!:
If the [STOP/RESET] key is set at Not ac-
tive [0] in parameter 014 Local stop/reset,and
there is no stop command via the digital inputs or
serial communication, the motor can only be
stopped by disconnecting the mains voltage to the
frequency converter.
[START] is used for starting the frequency converter.
It is always active, but the [START] key cannot over-
ride a stop command.
Manual initialisation
Disconnect mains voltage. Hold the [QUICK MENU]
+ [+] + [CHANGE DATA] keys down while simultane-
ously reconnecting the mains voltage. Release the
keys; the frequency converter has now been pro-
grammed for the factory setting.