Fault tracing

7.
F
AULT TRACING
When an unusual operating condition is detected by the AC drive control diagnostics, the drive
initiates a notification visible, for example, on the keypad. The keypad will show the ordinal
number of the fault, the fault code and a short fault description.
The fault can be reset with the Reset button on the control keypad or via the I/O terminal. The
faults are stored in the Fault history menu which can be browsed. The different fault codes you
will find in the table below. This fault table presents only the faults related to the fieldbus in
use.
NOTE: When contacting distributor or factory because of a fault condition, always write down
all texts and codes on the keypad display and send a description of the problem together with
Drive Info File
the
to fieldbus@vacon.com.
7.1
Typical fault conditions
Fault condition
Termination
Missing or excessive termination resistor.
resistor
• Supply or motor cables are located
too close to the fieldbus cable
Cabling
• Wrong type of fieldbus cable
• Too long cabling
Grounding
Inadequate grounding.
Faulty connections.
• Excessive stripping of cables
Connections
• Conductors in wrong terminals
• Too loose connections of conductors
• Faulty address
• Overlapping slave addresses
Parameter
• Wrong baud rate
• Wrong control place selected
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
Possible cause
Table 14. Typical fault conditions
Remedy
Install termination resis-
tors at both ends of the
fieldbus line.
Ensure grounding in all
points on the net
vacon • 30
7