vacon • 82
8.5

Fault tracing

Fault
Fault name Subcode
code
1
Overcurrent
Overvoltage
2
Earth fault
3
System Fault
8
8
Possible cause
AC drive has detected too high a
current (>4*I
) in the motor cable:
H
• sudden heavy load increase
• short circuit in motor cables
• unsuitable motor
The DC-link voltage has exceeded
the limits defined.
• too short a deceleration
time
• brake chopper is disabled
• high overvoltage spikes in
supply
• Start/Stop sequence too fast
Current measurement has
detected that the sum of motor
phase current is not zero.
• insulation failure in cables
or motor
84
MPI communication crc error
89
HMI receives buffer overflow
90
Modbus receives buffer overflow
93
Power identification error
97
MPI off line error
98
MPI driver error
99
Option board driver error
100
Option board configuration error
Table 57. Fault codes and descriptions.
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Remedy
Check loading.
Check motor.
Check cables and connections.
Make identification run.
Check ramp times.
Make deceleration time longer.
Use brake chopper or brake resistor
(available as options).
Activate overvoltage controller.
Check input voltage.
Check motor cables and motor.
Reset the fault and restart.
Should the fault re-occur, contact the
distributor near to you.
Check PC-drive cable.
Try to reduce ambient noise
Check Modbus specifications for
time-out.
Check cable length.
Reduce ambient noise.
Check baudrate.
Try to reduce ambient noise.
Reset the fault and restart.
Should the fault re-occur, contact the
distributor near to you.
Reset the fault and restart.
Should the fault re-occur, contact the
distributor near to you.
Reset the fault and restart.
Should the fault re-occur, contact the
distributor near to you.
Check contact in option board slot
Try to reduce ambient noise;
Reset the fault and restart.
Should the fault re-occur, contact the
distributor near to you.
Check contact in option board slot
Try to reduce ambient noise;
Should the fault re-occur, contact the
distributor near to you.