TTF200 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF200-EN REV. A
8.2.1

Error messages on the LCD display

If the event of an error, a message consisting of a symbol or letter (device status) and a number (DIAG NO.) will appear at the bottom of the process display.
Process display
Application F72
The diagnostic messages are divided into the following
groups in accordance with the NAMUR classification
scheme:
Symbol -
Description
Letter
I
OK or
Information
C
Check Function
S
Off
Specification
M
Maintenance
Required
F
Failure
Additionally, the diagnostic messages are divided into the
following areas:
Range
Description
Electronics
Diagnosis for device hardware.
Sensor
Diagnosis for sensor elements and
connection lines.
Installation /
Diagnosis for communication interface and
Configuration
parameterization / configuration.
Operating
Diagnosis for ambient and process
conditions
conditions.
NOTICE
For a detailed description of the errors and information on
troubleshooting, see chapter 'Possible HART error
messages' on page 30 .
Change from two to one column
Device is functioning or
information is available
Device is undergoing
maintenance (e. g. simulation)
Device or measuring point is
being operated outside of the
specifications
Request service to prevent the
measuring point from failing
Error; measuring point has failed

9 Diagnosis / error messages

The transmitter signals messages and errors in different
ways.
Messages via the HART interface
The transmitter signals changed configuration or parameter
setting by setting the HART flag "Configuration-changed"
(Configuration-changed).
The message can be acknowledged via the HART-DTM.
Error message on the LCD display
In the event of an error, a message appears at the bottom of
the process display,
consisting of a symbol or letters
(Device Status) and a number (DIAG.NO.).
See chapter 'Error messages on the LCD display' on page 29
.
Error message on the current output
Sensor or device errors can be indicated by underranging or
overranging of the current output.
Configuration takes place via the DTM parameter "<Current
output / output upon error>".
29

Advertisement

Table of Contents
loading