Commissioning; General Remarks; Checks Prior To Commissioning; Communication - ABB TTF200 Operating Instruction

Field-mount temperature transmitter
Hide thumbs Also See for TTF200:
Table of Contents

Advertisement

TTF200 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF200-EN REV. A
7

Commissioning

7.1

General remarks

In case of corresponding order the transmitter is ready for
operation after mounting and installation of the
connections.
The parameters are set at the factory.
The connected lines must be checked for firm seating. Only
firmly seated lines ensure full functionality.
7.2

Checks prior to commissioning

The following points must be checked before
commissioning the device:
— The wiring must have been completed as described in
chapter 'Electrical connections' on page 16 .
— The ambient conditions must meet the requirements set
out on the name plate and in the Datasheet.
7.3

Communication

NOTICE
The HART protocol is not secure, as such the intended
application should be assessed to ensure that these
protocols are suitable before implementation.
Communication with the transmitter takes place using the
HART protocol. The communication signal is modulated
onto both wires of the signal line in accordance with the
HART FSK "Physical Layer" specification.
The HART modem is connected at the signal line of the
current output via which power is also supplied via the
power supply unit.
+
1
-
2
3
Fig. 24: HART connection (example), R
1 Transmitter 2 Handheld Terminal 3 HART-Modem 4 PC
with FDT / DTM, EDD 5 Grounding (optional) 6 Power supply
unit (Process Interface)
1) if required
Change from two to one column
6
R = 250 Ω
1)
b
5
4
A10081
Load
B
HART Communication
Terminals
+ / -
Manufacturer ID
0x1A
Device Type ID
0x0D
Profile
HART 5.1
Configuration
DTM, EDD
Transmission signal
BELL Standard 202
Operating modes
— Point-to-point communication mode – standard (general
address 0)
— Multidrop mode (addressing 1 ... 15)
— Burst mode
Diagnostic message
— Overrange / underrange in accordance with NE 43
— HART diagnosis

7.4 Parameterization of the device

NOTICE
The device does not have operating elements for
parameterization on site.
Parameterization takes place via the HART interface.
Parameterization of the device takes place via standard
HART tools. These include:
— ABB handheld HART communicator DHH805 (TTX200
EDD)
— ABB Asset Vision Basic (TTX200 DTM)
— ABB 800xA control system (TTX200 DTM)
— ABB Field Information Manager (FIM)
— Other tools supporting standard HART EDDs or DTMs
(FDT1.2)
NOTICE
Not all tools and frame applications support DTMs or EDDs
at the same level. In particular, optional or advanced EDD /
DTM functions may not be available on all tools.
ABB provides frame applications supporting the full range
of functions and performance.
23

Advertisement

Table of Contents
loading

Table of Contents