Troubleshooting - Danfoss ERC 113 Reference Manual

Bottle cooler controller
Table of Contents

Advertisement

User manual

Troubleshooting

Problem
Compressor does not start
Fan does not start
Defrost does not start
Alarm does not sound
Display brightness is weak
Shift between ECO and normal mode does not
happen on ambient light change
Display alternates between condenser and
temperature
Display alternates between high and
temperature
Display alternates between low and
temperature
Display shows "dEf"
Alarm
Trigger
code
"Hi"
Air temperature is higher than
"ALA->Hat" for "ALA->Htd"
"Lo"
Air temperature is lower than
"LAt" for "Ltd"
"Con"
Condenser temperature is too
high or too low
"dor"
Door open for more than
"ALA -> dod"
"uHi"
Line voltage is higher than
"Cop->uHi"
"uLi"
Line voltage is lower than
"Cop->uLi"
"LEA"
Compressor continuous
running for more than
"ALA->LEA"
"E01"
"S1" error
"E02"
"S2" error
"E03"
"S3" error
"E04"
"S4" error
22
ERC 113 refrigeration controller
Probable cause
Waiting for compressor delay timer
Defrost in progress
Line voltage to compressor too low
or too high
Door is open or door contact is defective
Controller in pull down mode
Alarm delayed
Ambient light sensor broken
Ambient light sensor broken
or light level not set properly
Condenser too hot
Temperature too high
Temperature too low
Defrost in progress
Automatic
Outputs
clearance
User configured
Blink "Hi" with the highest temperature; If configured:
cut in alarm relay, beep the buzzer
User configured
Blink "Lo" with the lowest temperature. If configured:
cut in alarm relay, beep the buzzer
User configured
Blink "Con". If configured: cut in alarm relay, beep the buzzer
Always
Blink "dor". If configured: cut in alarm relay, beep the buzzer
Always
Blink "uHi". If configured: cut in alarm relay, beep the buzzer
Always
Blink "uLo". If configured: cut in alarm relay, beep the buzzer.
Always
Blink "LEA". If configured: cut in alarm relay, beep the buzzer
Always
Blink "E01". If configured: cut in alarm relay, beep the buzzer
Always
Blink "E02". If configured: cut in alarm relay, beep the buzzer
Always
Blink "E03". If configured: cut in alarm relay, beep the buzzer
Always
Blink "E04". If configured: cut in alarm relay, beep the buzzer
DKRCC.ES.RL0.F5.02
Remedy
Check CoP->CSt
Check CoP ->Pot /Pod
Check dEF ->dit, dot
Check CoP->uLi, uLo, uHi
Fan stops when door is opened
Check that door contact is ok
Defrost might be delayed during pull down
Check parameter Pud->Pdi
Check ALA->Htd, Abd
Check Pud->Pdd
Replace sensor
Check Eng->SLd, SLn
Clean condenser
Check Con ->CAL, CbL
Check ALA->HAt
Check ALA -> LAt
Check diS ->SdF
Comments
High temperature alarm
Low temperature alarm
Condenser alarm
Door open alarm
High voltage alarm
Low voltage alarm
Leakage alarm
"S1" sensor failure
(short or open)
"S2" sensor failure
(short or open)
"S3" sensor failure
(short or open)
"S4" sensor failure
(short or open)
Produced by Danfoss A/S (ADAP-KOOL®) | 2016-07