6 Commissioning
"
44
Performing a zero point adjustment
1.
Operate the system until normal operating conditions resume.
2.
Stop the flow (v = 0 m/s).
3.
Check the shut-off valves for leaks.
4.
Check that operating pressure is correct.
5.
Using the local display, select the "ZEROPOINT ADJUST" function in the function
matrix:
SITE SETUP → ZEROPOINT ADJUST → START
6.3
Data storage
If the power supply (via battery or adapter) fails, all the data are stored with the aid of a
lithium battery.
Caution!
In normal usage, the battery has a service life of about 5 years. When the battery has
reached the end of its service life, all data stored in the memory will be lost, see
Section 9 "Trouble- shooting".
For replacement, please contact E+H.
Prosonic Flow 92
Endress+Hauser
Need help?
Do you have a question about the prosonic flow 92 and is the answer not in the manual?