Properties
● BaseUnit suitable for all PotDis terminal blocks of the type "P1/P2/N0/P0". Can be
recognized by the laser inscription on the front and/or the last two digits of the article
number.
– Supply voltage (terminal P1, P2) up to DC 48 V/10 A
– Current carrying capacity per terminal: Max. 10 A
● BaseUnit opens up a new PotDis potential group. The self-assembling voltage buses P1,
P2 and the AUX busbar are disconnected from the adjacent module on the left (BaseUnit,
CPU, interface module).
● 18 terminals
– 17 red terminals (P1)
– 1 blue terminal (P2)
● 36 terminals (with PotDis-TB)
● Connection system in the form of push-in terminals
6.2.3

Connecting

Pin assignment
Terminal
P1
P2
BaseUnits (6ES7193-6BP.../3RK1908-0AP00...)
Manual, 02/2018, A5E03727049-AJ
NOTICE
Opening a potential group for I/O modules is not permitted with the BaseUnit PotDis-
BU-P1/D-R.
The BaseUnit PotDis-BU-P1/D-R opens a new potential group only for the potential
distributor modules. Opening a potential group for I/O modules is not permitted with the
BaseUnit PotDis-BU-P1/D-R.
Pin assignment for BaseUnit PotDis-BU type P1, light-colored version
Rated supply voltage up to 48 V DC with max. 10 A (17 red terminals)
Ground (1 terminal)
Potential distributor modules
6.2 PotDis-BU type P1, light-colored version
Explanation