Connection - Siemens SIMATIC ET 200SP Manual

6es7193-6bp series; 3rk1908-0ap00 series
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Properties
● BaseUnit suitable for all fail-safe and non-fail-safe SIMATIC ET 200SP High Feature
motor starters
● The BaseUnit takes over the potential group (P1, P2) from the adjacent module on the
left.
● The BaseUnit opens a new supply group 500 V AC. The potential group (24 V DC) is
further continued
● Connection method using push-in terminals
● The touch protection cover for the infeed bus is included in the scope of delivery.
● The fail-safe input F-DI of the fail-safe motor starter is connected to the power bus.
Maximum configuration of the infeed bus (500 V AC)
The number of motor starters that can be used per infeed group depends on the following
factors:
1. Total current requirement of all motor starters operated on this infeed group.
2. Ambient temperature and installation type in which the motor starters are operated.
You can find further information in the derating table in the Manual SIMATIC ET 200SP
motor starters.
5.3.2

Connection

Pin assignment
Terminal
L1(L), L2(N), L3, PE
T1, T2, T3, PE
BaseUnits (6ES7193-6BP.../3RK1908-0AP00...)
Manual, 02/2018, A5E03727049-AJ
5.3 BU30-MS2 - BaseUnit with 500 V AC infeed
Pin assignment for BaseUnit with 500 V AC infeed
Power supply
Assignment is determined by the motor starter. See Manual ET 200SP
motor starters
(https://support.industry.siemens.com/cs/ww/en/view/109479973).
Motor feeder
BaseUnits for motor starters
Descriptions
93