2.3

Wiring

(1) Strip the signal wires as shown below. If too much of the wire is stripped, a short circuit may occur with neighboring wires.
If not enough of the wire is stripped, wires may become loose and fall out.
Twist the stripped end of wires to prevent them from fraying. Do not solder it.
Wire strip length
Use appropriate crimp terminals (ferrules, blade terminals, etc.) for these terminal blocks as necessary.
When using the crimp terminal, make sure that the stranded wire do not come out of the terminal.
NOTE
• Crimp terminals commercially available (as of January 2017. The product may be changed without notice.)
Terminal
Wire size (mm
screw size
0.3
M2
0.5
12
INSTALLATION AND WIRING
5 mm
Damaged
Ferrule part No.
2
)
With insulation sleeve
AI 0,34-6TQ
Al 0,5-6WH
Unstranded
wires
Wires are not inserted
Crumpled tip
into the sleeve
Without insulation sleeve
A 0,34-7
A 0,5-6
Crimping tool
Manufacturer
model No.
Phoenix Contact
CRIMPFOX 6
Co., Ltd.