Omron NT631 Operation Manuals page 270

Programmable terminal
Hide thumbs Also See for NT631:
Table of Contents

Advertisement

Areas for Control/Notification
Reference
262
[Screen switch setting in the PT status control area]
15 14 13 12 11 10 9
Word
Screen number (4-digit BCD or hexadecimal)
n
The screen numbers that can be set are as follows.
BCD
0000
0000
H
0001 to 3999
0001 to 0F9F
H
9001
2329
H
9002
232A
H
- The screen can also be switched by bit memory table operation (page 468), by
touch switch operation (page 469), or by using the alarm list/history function
(page 472).
- To display overlapping screens, designate the screen number of the parent
screen.
- If there are no elements registered for the designated screen number, or if a key-
board screen is designated, the screen does not switch.
- When the NT631/NT631C starts operating, the screen is displayed according to
the contents of the "screen switch setting" word. If the contents of the "screen
switch setting" word are invalid, the screen is displayed according to the "Initial
Screen" in the PT configuration settings made at the Support Tool. If the setting
for "Initial Screen" is also invalid, an error message is displayed.
- When data is written from the NT631/NT631C
When the screen display has been switched by operation at the
NT631/NT631C, the new screen number is written as a 4-digit BCD or hexade-
cimal value into the "screen switch setting" word by the NT631/NT631C. At
the same time, the "ON" status is also notified to the screen switch strobe flag
of the "PT status" word of the PT status notify area by the NT631/NT631C (af-
ter notification, the OFF status is re-established) (page 474). Whether the
data is written in BCD or hexadecimal format is determined by the setting for
"numeral storage type" in the PT configuration settings made at the Support
Tool.
NT631/NT631C
Currently displayed
screen
8
7
6
5
4
Hexadecimal
No-display (screen cleared)
H
(3999)
Screen numbers 1 to 3999
H
(9001)
Occurrence history screen
H
(9002)
Frequency history screen
H
PC
PT status control area
Screen switch setting
Copy memory
table setting
PT status control setting
Reserved for system use
PT status notify area
Content update memory table
PT status
Section 7-2
3
2
1
0
Bit
Screen switch setting
Screen
← Screen number
← Screen switch strobe flag

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nt631c

Table of Contents