Technical Data - Fronius Symo 3.0-3-S Operating Instructions Manual

Grid-connected inverter
Hide thumbs Also See for Symo 3.0-3-S:
Table of Contents

Advertisement

Technical data

Fronius Symo
Input data
MPP voltage range
Max. input voltage
(at 1,000 W/m² / -10 °C in an open circuit)
Min. input voltage
Max. input current
Max. short circuit current of the solar mod-
ules (I
)
SC PV
4)
Max. feedback current
Output data
Nominal output power (P
Max. output power
Nominal grid voltage
Min. grid voltage
Max. grid voltage
Nominal output current at 220 / 230 V
Max. output current
Nominal frequency
Total harmonic distortion
cos phi power factor
Power-up current pulse
Max. output fault current per period
General data
Maximum efficiency
European efficiency
Overnight self-consumption
Cooling
Degree of protection
Dimensions h x w x d
Weight
Permissible ambient temperature
Permitted humidity
EMC device class
Overvoltage category DC / AC
Pollution level
Noise emission
Protection devices
DC insulation measurement
Response to DC overload
DC disconnector
RCMU
54
)
nom
6)
and duration
3.0-3-S
200 - 800 V DC
250 - 800 V DC
32 A (RMS)
3000 W
3000 W
3~ NPE 400 / 230 V or 3~ NPE 380 / 220 V
150 V / 260 V
280 V / 485 V
4.5 / 4.3 A
0.7 - 1 ind./cap.
21.4 A / 1 ms
96.2%
< 0.7 W & < 3 VA
Controlled forced-air ventilation
645 x 431 x 204 mm
- 25 °C - +60 °C
58.3 dB(A) ref. 1pW
Operating point shift, power limitation
3.7-3-S
300 - 800 V DC
1000 V DC
150 V DC
16.0 A
24.0 A
5)
3700 W
3700 W
5.6 / 5.4 A
6.8 / 6.5 A
9 A
1)
50 / 60 Hz
< 3%
2)
38 A / 2 ms
98%
96.7%
IP 65
16 kg
0 - 100%
B
2 / 3
2
Integrated
Integrated
Integrated
4.5-3-S
4500 W
4500 W
97%