WIRING DIRECTIONS

Watt Stopper B series power packs supply power for up to 5 CI-200s.
When using more sensors than this, multiple power packs are required.
For all configurations—connect the low voltage:
• RED wire (+24VDC) from power pack to VIOLET wire on sensor.
BLACK wire (Return) from power pack to GREEN wire on sensor.
Connections for the following configurations:
(Refer to wiring diagram below)
Single lighting load controlled by occupancy only—connect:
• BLUE wire from power pack to yellow wire on sensor.
Single lighting load controlled by occupancy, dependent on light level
(ambient light)—connect:
• BLUE wire from power pack to blue wire on sensor.
One lighting load for occupancy control, and a second load
for occupancy and light level (ambient light) control—connect:
• BLUE wire from power pack to yellow wire on sensor.
• BLUE wire from slave pack to blue wire on sensor.
• BLACK wire from slave pack to gray wire on sensor.
Isolated Relay
(The Isolated Relay is rated for 1A @24VDC or 24VAC)
Connect the wires necessary to the application that requires this output.
• RED (Common) (must be used for proper operation)
• BROWN (Normally Closed)—Open when occupancy is detected.
• ORANGE (Normally Open)—Closed when occupancy is detected.
White
N
Black
Hot
SLAVE
PACK
Blue
Black
OFF switch
Hot
Red (load)
N
Check Our Web Site For FAQs: www.wattstopper.com
CAUTION
TURN POWER OFF AT CIRCUIT
BREAKER BEFORE WIRING SENSOR
White (Neutral)
POWER PACK
Red (Line)
Red (Load)
Isolated Relay Outputs
Normally Closed Contact
Common
Normally Open Contact
Control Output 24VDC
Light Level Output 24VDC
Light
Level
Lighting
Load
Lighting
Load
Switch
Wires
1-BRN
2-RED
3-ORN
4-YEL
Control Return
5-GRN
6-BLU
+24VDC
7-VIO
Common
8-GRA
CI-200