SENSOR ADJUSTMENT

The sensor comes factory preset and ready for
operation. If testing of operation is desired:
• Remove the sensor's cover (twist).
• Refer to the DIP switch settings chart below
for switch configurations.
• Make sure that office furniture and fixtures are
in place.
1. Restore power to the lighting circuits
and turn the lights on.
• There is a one minute warm-up
when power is initially restored
to the sensor before the sensor
works properly.
2. For testing, set the Time Delay to
minimum (15 secs.).
3. Set Sensitivity to maximum.
4. Turn Light Level Adjustment trimpot
to maximum.
5. Replace the sensor's cover then
move away from sensor and be still.
The lights should go off after 15
seconds. If lights remain on, see
Unwanted Sensor Activations under
Troubleshooting.
With movement in the area, the
lights should turn back on.
6. If using the light level feature
(otherwise skip to step 7), turn the
adjustment trimpot to minimum, and
repeat step 5. Unless it is very dark,
when the lights turn off, the lights
controlled by light level should not
turn back on even with movement in
the area.
Until ready to make the final adjustment, leave the setting at maximum.
The controlled lights will then not be affected by ambient light levels.
To make the light level adjustment: (The final light level setting for
normal operation should be made at a time when, with the lights off,
the ambient light level is at the point where it is desired for the lights
to turn on.)
Set the Time Delay and the Light Level to minimum, then be still
until the lights turn off (about 15 seconds). Slowly turn the light level
adjustment toward maximum until the lights turn on—then turn it back
slightly. At this setting the lights will not turn on if ambient light levels
are above the current level.
7. Set the desired Time Delay for operation (DIP switches #1 – 6).
Factory preset Time Delay is 20 minutes; other suggestions are:
Offices and conference rooms (10 minutes), Classrooms (10 minutes),
Warehouses (6 minutes), Hallways (4 minutes).
Call 800.879.8585 For Technical Support
DIP Switch Control
for Time Delay and
Sensitivity
Light Level
Adjustment
DIP Switch #
Time delay
15 seconds
2 minutes
4 minutes
6 minutes
8 minutes
10 minutes
12 minutes
14 minutes
16 minutes
18 minutes
20 minutes
22 minutes
24 minutes
26 minutes
28 minutes
30 minutes
Service
DIP Switch #
Sensitivity
Minimum
Medium Low
Medium High
Maximum
= ON
= OFF
= Factory Presets
MAX
MIN
LED
1 2 3 4 5 6
7 8