WIRING AND INSTALLATION

TURN POWER OFF AT THE CIRCUIT BREAKER BEFORE INSTALLING SENSOR.
SENSOR MUST BE INSTALLED BY QUALIFIED PERSONNEL ONLY.
Wire connections for sensor (see instructions, page 6)
Gasket
IMPORTANT! thread wires through
gasket before connecting
To Controlled
Loads
4" round
outdoor
junction box
NOTE: Weather proof caulking may be required
around junction box and cover plate to provide a
weatherproof seal in some installations.
Wire connections when attaching lamp holders (Isolated relay wires not shown)
Gasket
IMPORTANT! thread wires through
gasket before connecting
To additional
Controlled Loads
(optional)
4" round
outdoor
junction box
NOTE: Weather proof caulking may be required
around junction box and cover plate to provide a
weatherproof seal in some installations.
5
Check Our Web Site For FAQs: www.wattstopper.com
CAUTION
Attach cover plate assembly and
gasket to the junction box with 4
screws and screw covers (supplied)
Cover
plate
IMPORTANT! Make sure that the
gasket seats properly when attaching
the cover plate
Isolated Relay Wires (N/O, COMMON, N/C)
Model #s: EW-100 & EW-200
Attach cover plate assembly and
gasket to the junction box with 4
screws and screw covers (supplied)
Cover
plate
IMPORTANT! Make sure that the
gasket seats properly when attaching
the cover plate
Lamp holder
(CANLET
®
lamp holder shown)
WIRING AND INSTALLATION (continued)
Wire the sensor as shown below:
• BLACK wire from sensor to line voltage.
• WHITE wire from sensor to Neutral.
• RED wire is connected to lighting loads, if used, as shown (see diagram above and below),
not to exceed load rating (see Specifications, front cover).
• Isolated Relay (see Specifications, front cover, for rating). Connect the wires necessary
to the application that requires this output.
- ORANGE (Common) (must be used for proper operation).
- GREEN (Normally Closed) (Open when occupancy is detected).
- YELLOW (Normally Open) (Closed when occupancy is detected).
Multiple sensors (optional)
connected in parallel
Black
White
Switch
(optional)
Black
Black
Line
White
White
Neutral
Note: When power is restored to the sensor, the lights will turn on. If no motion is detected by
the sensor, the lights will remain on for the set time delay period (or minimum of approximately
one minute) and then turn off (see Security Override, page 9).
Call 1(800) 879-8585 or 1(972)578-1699 For Technical Support
Red (Load)
Sensor
Red (Load)
Sensor
Isolated Relay
Load
Orange (Common)
Green (Normally Closed)
Yellow (Normally Open)
Multiple loads (optional)
connected in parallel
Load
6