(13) CC-Link module
• To ground the Ver.1.10-compatible CC-Link dedicated cable,
(3)(c) in this section.
• Each power line connecting to the external power supply
terminal or module power supply terminal must be 30m or less.
• Install a noise filter to the external power supply. Use the noise
filter having an attenuation characteristic, MA1206 (TDK-
Lambda) or equivalent. Note that a noise filter is not required if
the module is used in Zone A defined in EN61131-2.
• Keep the length of signal cables connected to the analog input
terminals of the following modules to 30m or less.
• Wire cables connected to the external power supply and module
power supply terminal in the control panel where the module is
installed.
• AJ65BT-64RD3
• AJ65BT-64RD4
• AJ65BT-68TD
• For the cable connected to the power supply terminal of the
AJ65SBT-RPS, AJ65SBT-RPG or AJ65BT-68TD, attach a ferrite
core with attenuation characteristic equivalent to that of the
ZCAT3035-1330 from TDK Corporation. Twist the cable around
the ferrite core by one as shown below.
55