An error message is displayed

If Error 185 Meter Comm. Error is displayed in the meter status screen, verify proper connection of:
 
The RS485 cables and connectors
l
 
The AC connection of the meter
l

Total [Wh] Import value is not advancing

If the inverter is not producing power, and there is power consumption by the loads, the Total [Wh] 
value should be changing.
If the Total [Wh] value of the Import meter displays a steady value although the site is consuming power, 
check the following:
 
The meter status LEDs are lit. If the LEDs are all OFF, the meter is not connected to a power source. 
l
 
Check the meter AC connection (10-pin terminal block)
o
 
Check that the meter breaker is ON
o
 
There are no loose connections at the 10-pin AC wiring of the meter. 
l
 
The CT black and white cables are correctly connected to the 6-pin connector on the meter:
l
 
White CT wire is connected to L1 white 
o
 
Black CT wire is connected to L1 black 
o
 
CT direction is towards the grid and the green power LEDs are ON. If the LEDs are not green indicating 
l
import power - the CTs are reversed.
 
SolarEdge-StorEdge Installation Guide MAN-01-00262-1.0
Figure 40: Meter with CT
Appendix A: Troubleshooting
81