Storedge Connection Unit Leds; Power Optimizer Troubleshooting - SolarEdge StorEdge Installation Manual

Hide thumbs Also See for StorEdge:
Table of Contents

Advertisement

StorEdge Connection Unit LEDs

The warning is a status screen. To view the warning description, press the LCD button.The following is a 
list of system warnings:
Warning #
1-4, 6-7
Fan X Failure
5
Turn Switch Off to Configure
8
Connection Unit Low 9V Battery
StorEdge Connection Unit LEDs
There are three LEDs on the lower board of the StorEdge Connection Unit, near the DIP switches: 
In normal operation, t he middle and bottom LEDs indicate auxiliary voltages (13V from DC/DC, 5V
l
and 3.3V) and should always be  lit.  
The top LED should be lit when the inverter DC voltage is at least 200 Vdc (check when both inverter
l
ON/OFF switch and StorEdge Connection Unit switch are ON). You can check the status screen for 
the Vdc value.
If all LEDs are OFF: 
l
 
Check that AC voltage exists in the inverter
o
 
Check that the communication cable between the StorEdge Connection Unit and the digital 
o
board is properly connected.
If the top LED is ON, and middle and bottom LEDs are off - an internal failure has occurred. Contact 
l
SolarEdge support.

Power Optimizer Troubleshooting

If the inverter status screen indicates that not all power optimizers are paired or not all are reporting (P_
OK xxx/yyy, and x<y), those optimizers can be identified through the LCD. Refer to 
http://www.solaredge.com/files/pdfs/products/inverters/non-responding-power-optimizers.pdf
88
LCD text
Figure 41: StorEdge Connection Unit LEDs
SolarEdge-StorEdge Installation Guide MAN-01-00262-1.0
Comments and troubleshooting
Clean or replace the fan
Appears when trying to access the Setup
menus during production
Replace the 9V battery in the StorEdge
Connection Unit. Refer to 9V Battery
Replacement on page 91.