13 Menu's and Advanced Configuration

13.1 Abort Function

In Review Mode or Configuration Mode the user can escape one step back from the
current position using the Abort Function. To do this the user must activate the Enter
switch for more than 3 seconds with the Magnetic Wand. Switching between each pair of
modes or between menus and sub menus are shown in the following table.
From
Review Mode
Configuration Mode Monitoring Mode

Configuration Mode

sub menu
13.2 Configuration Mode
The table below shows the functions available via the configuration menu that can be
displayed on the transmitter and accessed using the Magnetic Wand.
The instrument will show the main Menu when the "Enter" switch is activated with the
Magnetic Wand and held for at least 3 seconds.
The Menu is password protected to prevent any unauthorized changes. The password is
initially disabled and the default password is '0000'. If the default password is changed
to other than '0000', then the password is enabled automatically and requested when
entering Configuration Mode.
With the Menu showing, the following functions can be performed: calibration, bump test,
sensor selection and configuration of parameters such as measuring range, calibration
gas level, calibration interval, inhibit current, inhibit timeout, alarm setting, relay setting,
password change, location setting, temperature unit reading, force analogue output and
alarm function checks.
While in Configuration mode, the output current of the transmitter is inhibited to prevent
false alarms.
Names, displays and descriptions for each menu item in Configuration Mode are shown in
the following table.
To
Monitoring Mode
Configuration Mode
main menu
Table 10: Transmitter menu switching
SPXCDHMRFENU Issue 1
Example
Activate Enter switch for more than 3
seconds while in Review Mode
Activate Enter switch for more than 3
seconds while navigating menus in the
Configuration Mode
Activate Enter switch for more than 3
seconds while in a sub menu
36