The specifications are only an overview and refer to the measuring cell. Limitations due to the ma-
terial and version of the process fitting are possible. The specifications on the nameplate apply.
Nominal range
Gauge pressure
0 ... +3 psig
0 ... +6 psig
0 ... +15 psig
0 ... +35 psig
0 ... +70 psig
0 ... +150 psig
0 ... +350 psig
0 ... +900 psig
Reference conditions and actuating variables (according to DIN EN 60770-1)
Reference conditions according to DIN EN 61298-1
Ʋ Temperature
Ʋ Relative humidity
Ʋ Air pressure
Determination of characteristics
Characterstic curve
Reference installation position
Influence of the installation position
Deviation determined according to the limit point method according to IEC 60770
Applies to the digital signal output (HART, Profibus PA, Foundation Fieldbus) as well as to ana-
logue current output 4 ... 20 mA and refers to the set span. Turn down (TD) is the ratio nominal
measuring range/set span.
Deviation
Ʋ Turn down 1 : 1 up to 5 : 1
Ʋ Turn down > 5 : 1
Influence of the product or ambient temperature
Average temperature coefficient of the zero signal and the output span
Applies to the digital signal output (HART, Profibus PA, Foundation Fieldbus) as well as to ana-
logue current output 4 ... 20 mA and refers to the set span. Turn down (TD) is the ratio nominal
measuring range/set span.
Incl. non-linearity, hysteresis and non-repeatability.
12)
VEGABAR 66 • 4 ... 20 mA/HART - climate compensated
Overload capacity, max.
pressure
+500 psig
+700 psig
+700 psig
+950 psig
+950 psig
+1300 psig
+1900 psig
+2900 psig
+15 ... +25 °C (+59 ... +77 °F)
45 ... 75 %
860 ... 1060 mbar/86 ... 106 kPa (12.5 ... 15.4 psig)
Limit point adjustment according to IEC 61298-2
Linear
upright, diaphragm points downward
< 0.2 mbar/20 Pa (0.003 psig)
< 0.1 %
< 0.02 % x TD
10 Supplement
Overload capacity, min. pres-
sure
-15 psig
-15 psig
-15 psig
-15 psig
-15 psig
-15 psig
-15 psig
-15 psig
12)