Vega VEGABAR 66 Operating Instructions Manual page 35

Suspension pressure transmitter with certec measuring cell
Table of Contents

Advertisement

Carry out a position cor-
rection
Carry out min. adjustment
VEGABAR 66 • 4 ... 20 mA/HART - climate compensated
4. Confirm with [OK], the submenu "Density unit" appears.
Unit of measurement
Density unit
kg/dm³
pcf
5. Select the requested unit, e.g. kg/dm³ with [->] and confirm with
[OK], the submenu "Density" appears.
Unit of measurement
Density
0001000
kg/dm³
6. Enter the requested density value with [->] and [+], confirm with
[OK] and move to position correction with [->].
The adjustment unit is thus switched over from bar to m.
Proceed as follows to select the temperature unit:
1. Activate the selection with [OK] and select "Temperature unit
with [->].
2. Activate the selection with [OK] and select the requested unit with
[->] (e.g. °F).
3. Confirm with [OK].
The temperature unit is hence switched over from °C to °F.
Proceed as follows:
1. Activate in the menu item "Position correction" the selection with
[OK].
Position correction
Offset
=
+0000 mbar
P
53 mbar
2. Select with [->], e.g. to accept actual measured value.
Position correction
Accept current measured
value?
Accept
Edit
3. Confirm with [OK] and move to min.(zero) adjustment with [->].
Proceed as follows:
1. Edit the % value in the menu item "Min. adjustment" with [OK].
2. Set the requested percentage value with [+] and [->].
3. Confirm with [OK] and edit the requested mbar value.
Selection options: °C, °F.
4)
6 Set up with the display and adjustment module PLICSCOM
4)
Min. adjustment
+000.0 %
=
+0000.0 mbar
0000.0 mbar
35

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents