Table Profibus - janitza Prophi Operating Instructions Manual

Reactive power controller
Table of Contents

Advertisement

Reactive Power Controller

Table Profibus

Description
PEW PAW Format
Current
0
Voltage L-L
2
Reactive power
4
Cos(phi)
6
Outputs
8
Alarm outputs
10
Outputs, remote
Attention!
m
The Current and voltage transformer ratios are not mentioned for measured values.
= Key 1
unit
word
mA
word
V
word
Var
word
word
word
0
word
= Key 2
= Key 3
Comment
Urated +10% -15%
+ = cap, - = ind
+ = cap, - = ind
Bit 0 K1
(1=On, 0=Off)
Bit 1 K2
Bit 2 K3
..
..
Bit 11 K12
Bit 12 Alarm output
Bit 0 Low voltage
Bit 1 Over voltage
Bit 2 Current too low
Bit 3 Current too high
Bit 4 Insufficient capacitor power
Bit 5 Supply of real power
Bit 6 Harmonic limits exceeded
Bit 7 Over temperature
Bit 0 K1
(1=On, 0=Off)
Bit 1 K2
Bit 2 K3
..
..
Bit 11 K12
Bit 12 free
Bit 13 Tariff
Bit 14 Remote Tarif
Bit 15 Remote Outputs