Ventilator Control; Ventilation Control; Upper Temperature Limit; Lower Temperature Limit - janitza Prophi Operating Instructions Manual

Reactive power controller
Table of Contents

Advertisement

Reactive Power Controller

Ventilator control

With the temperature
feeler, inserted in
Prophi, and a ventila-
tor, a simple ventilator
control can be estab-
lished.
Therefore, an
upper temperature limit, a
lower temperature limit and a

switching output

must be fixed.
Please note, that the inner temperature of the Prophi is
about 2°C over the outer temperature.
A relay output or the alarm output (option) serves as
ventilator output.
If the switching output 0 is assigned to the ventilator
control, the ventilator control is not active.
An upper and lower temperature limit can be set. The
temperature limits can be set in the range of 0°C and
98°C in 1° steps. While programming, you can only set
an upper limit, when it is at least 1°C over the lower
limit.
Attention! If an output is programmed for ventilator
control, and if it is also programmed for a fix stage or
alarm output, the ventilator control has higher priority.
= Key 1
Prog
Obere Grenztemperatur
= Key 2
= Key 3

Ventilation control

Using the temperature
sensor, which is in-
serted within Prophi, a
simple ventilation con-
trol can be built.
To reach this goal, an
Upper temperature limit, a
Lower temperature limit and
A switching output
must be determined.
While programming of temperature limits, please mind,
that the inner temperature of Prophi is about 2°C above
the outer temperature.
The temperature limits can be set in the range of 0°C
and 98°C in1°C steps.
While programming, it is only possible to set the upper
temperature limit, when it is at least 1°C above the
lower limit.

Upper temperature limit

If the upper limit is ex-
ceeded, the ventilation
is switched on.

Lower temperature limit

If temperature is below
the lower limit, the
ventilation is switched
off.
Switching output
One of the relay out-
puts or the alarm out-
put can be used as
switching output of
Prophi.
If output 0 is assigned
to the ventilation control, the ventilation control is in-
activated.
Attention!
m
If one output has been programmed for ventila-
tion control, and additionally, it is programmed
as a fix stage or alarm output, the ventilation
control has priority.
Prog
Upper temperature limit
(Ventilation control)
Prog
Upper temperature limit
(Ventilation control)
Prog
Lower temperature limit
(ventilation control)
Prog
No output selected
Page 35