Configuration Data; Setting Range; Manufacturer's Presetting - janitza Prophi Operating Instructions Manual

Reactive power controller
Table of Contents

Advertisement

Reactive Power Controller

Configuration data

Description
Target-cos(phi1)
Target-cos(phi2)
CT ratio
Learning of configuration
Stage power of 1. stage
Stage ratio
Switching outputs
Fix stages
Discharge time
Disconnection pause for relay stages
Switching frequency for semic. stages
Power station service
Stage power, 1. - 12. capacitor stages
Choke degree
VT ratio
Number 1 (Primary)
Number 2 (Secondary)
Harmonic table number
Alarm calls
Low voltage
Overvoltage
Current too low
Current too high
Insufficient capacitor power
Supply of real work
Harmonic limits exceeded
Overtemperature
Averaging time of reactive power
Averaging time for mean value cos(phi) 0.25, 0.50, 1.00, 2.00, 12.00, 24.00h
Ventilator control
Upper temperature limit
Lower temperature limit
Output number
Overtemperature disconnection
Upper limit
Lower limit
Pause time
Indication in manual mode
Password
Contrast
Reset programming
Connection configuration
Software Release
Serial number part 1
Serial number part 2
Serial interface
Device address
Protocol
Baud rate
Modbus RTU
Profibus DP V0
1) For inner temperatures of over 70°C an alarm is always raised.
2) If a switching frequency of 50Hz is programmed for the transistor outputs, the serial interface does not work!
= Key 1

Setting range

0.80cap. .. 1.00 .. 0.80ind.
0.80cap. .. 1.00 .. 0.80ind.
1 .. 9999
oN, oFF
0var .. 9999kvar
0 .. 9
1 .. 12
0 .. 3
0 .. 1200 seconds
0 .. 1200 seconds
0.1, 0.2, 0.5, 1.0, 10.0, 50.0Hz
on, oFF
0var .. 9999kvar
0 .. 15%
1 .. 9.999k
1, 10, 100, 110, 200, 230, 400
0 .. 10
on/1, oFF
on/2, oFF
on/3, oFF
on/4, oFF
on/5, oFF
on/6, oFF
on/7, oFF
on/8, oFF
0.1, 0.5, 1.0, 5.0, 10.0, 30.0, 60.0Sek.
0 .. 99°C
0 .. 98°C
0 .. 13 (13 = alarm output)
0 .. 99°C
0 .. 98°C
0 .. 1200 seconds
CoS = cos(phi), CAr = react. power
0 .. 9999
1 .. 12
0° .. 359°
x.xxx
xxxx
xxxx
0 .. 126
0 .. 1
0=9.6, 1=19.2, 2=38.4, 3=57.6, 4=115.2
Automatical adaption up to 1.5Mbps at maximum
= Key 2
= Key 3

Manufacturer's presetting

0.96ind
0.90ind
10
oFF
10kvar
1:1:1:1
all stages
0 = no fix stages
60 Sec.
40 Sec.
1)
1.0 Hz
oFF
10kvar
0 %
1
1
0
oFF
oFF
oFF
oFF
oFF
oFF
oFF
2)
oFF
60.00 Sec.
24.00 h
0°C
0°C
0 = no ventilator control
55°C
50°C
600 seconds
CAr = react. power
0000 = no password
6
000°
actual version
depending on device
depending on device
001
0
0 ( = 9.6kbps)
Page 53