Discharge Time; Disconnection Pause - janitza Prophi Operating Instructions Manual

Reactive power controller
Table of Contents

Advertisement

Reactive Power Controller

Discharge time

The discharge time
means the time, which
each capacitor stage
has got for discharge.
Setting range : 0 - 1200 seconds
The discharge time will be started after a net return and
after switching off a capacitor stage.
Capacitor stages controlled by transistor outputs must
not consider the discharge time, as the therewith con-
trolled semiconductor switches in the zero crossing of
voltage.
Example: Programming discharge time
With key 3 you can leaf to the discharge time in the
expanded programming. With key 1 you get into pro-
gramming mode. In this example a discharge time of
60 seconds is indicated.
Select the digit to be
changed using key 2.
The selected digit is
flashing.
Change digit using key
3.
Pressing key 1 you leave the programming mode and
with key 3 you can continue leafing through the ex-
panded programming.
Page 26

Disconnection pause

The
disconnection
pause means the time
after the connection of
s
a capacitor stage, in
Prog
which it is forbidden to
disconnect the next stage.
Setting range : 0 - 1200 seconds
The disconnection pause is not valid for capacitor stages,
switched via transistor outputs.
Example: Programming of disconnection pause
With key 3 you leaf to the disconnection pause in ex-
panded programming. Please press key 1. In this exam-
ple a disconnection pause of 15 seconds is indicated.
Select the digit to be changed by using key 2. The
selected digit is flash-
ing.
Change the selected
digit using key 3.
s
Prog
Pressing key 1 you leave the programming mode and
with key 3 you can continue leafing through the ex-
panded programming.
= Key 1
= Key 2
= Key 3
s
Prog
s
Prog

Hide quick links:

Advertisement

Table of Contents
loading