Panasonic WUME-SF4D-4 Instruction Manual page 101

Sf4d series safety light curtain type 4
Table of Contents

Advertisement

Manual reset: The control output (OSSD 1 / 2) does not automatically turn ON when the device
is in the light-receiving state. The control output (OSSD 1 / 2) turns ON when the
device is reset {test / reset input: (open) → [short (+V when using PNP output or
0V when using NPN output)] → (open)} in the light-receiving state.
<Timing chart>
Open (OFF)
Test / Reset input
Shorted (ON)
Light received
Light received
state
Light blocked
Control output
(OSSD 1 / 2)
Note: The response time depends on the number of beam channels.
Number of units in
series connection
Number of units in
parallel connection
4 to 48
49 to 96
97 to 127
128 to 144
145 to 192
193 to 256
Auto reset: The control output (OSSD 1 / 2) automatically turns ON when the device is in the light-receiving state.
<Timing chart>
Light received
Light received
state
Light blocked
Control output
(OSSD 1 / 2)
Note: The response time depends on the number of beam channels.
Number of units in
series connection
Number of units in
parallel connection
4 to 48
49 to 96
97 to 127
128 to 144
145 to 192
193 to 256
<Reference>
The conditions for interlock activation can be changed using the communication module
SF4D-TM1 (option) and Configurator Light Curtain software.
© Panasonic Industrial Devices SUNX Co., Ltd. 2017
ON
OFF
Main sensor
1 unit 2 units 3 units 4 units 0 unit 0 unit 1 unit 1 unit 2 units 2 units 3 units
1 unit
0 unit 0 unit 0 unit 0 unit 1 unit 2 units 1 unit 2 units 1 unit 2 units 1 unit
6ms
10ms 10ms 12ms 12ms 14ms 14ms 14ms 14ms 14ms 14ms 14ms
8ms
10ms 10ms 12ms 12ms 14ms 14ms 14ms 14ms 14ms 14ms 14ms
10ms
12ms 12ms 14ms 14ms 14ms 14ms 14ms 14ms 14ms 14ms 14ms
12ms 12ms 14ms 14ms 14ms 14ms 14ms 14ms 14ms 14ms 14ms
14ms 14ms 16ms 16ms 14ms 14ms
16ms 16ms 18ms 18ms
ON
OFF
Main sensor
1 unit 2 units 3 units 4 units 0 unit 0 unit 1 unit 1 unit 2 units 2 units 3 units
1 unit
0 unit 0 unit 0 unit 0 unit 1 unit 2 units 1 unit 2 units 1 unit 2 units 1 unit
6ms
10ms 10ms 12ms 12ms 14ms 14ms 14ms 14ms 14ms 14ms 14ms
8ms
10ms 10ms 12ms 12ms 14ms 14ms 14ms 14ms 14ms 14ms 14ms
10ms
12ms 12ms 14ms 14ms 14ms 14ms 14ms 14ms 14ms 14ms 14ms
12ms 12ms 14ms 14ms 14ms 14ms 14ms 14ms 14ms 14ms 14ms
14ms 14ms 16ms 16ms 14ms 14ms
16ms 16ms 18ms 18ms
150ms to 4 sec.
(Note)
Response time (OFF response)
Sub sensor
(Note)
Response time (OFF response)
Sub sensor
100ms or less
50ms or less
Functions