Installation and Wiring
4.2.3 Wiring for the Power Supply Part of the CPU Unit
When the CPU unit is used with 24V DC power supply, perform wiring for power supply as
follows.
Use the power supply cables (Part No.:AFPG805) that come with the unit to connect the
power supply.
Brown: 24V DC, Blue: 0V, Green: functional earth
Power supply part of the CPU unit
External power supply
Fed from an external power supply 24V DC
Power supply voltage
Confirm that the power supply voltage is within the allowable range of the power supply.
Rated input
voltage
24V DC
When a programmable display GT series is connected to the GT power supply terminal
(24V) of the CPU unit, use it within the range of 21.6 to 26.4 V DC.
Selection of a power supply
Referring to Section 1.2, select a power supply larger than the capacity of the unit.
In the minimum configuration, select a power supply of 24 W or larger.
In order to protect the unit against abnormal voltage from the power supply line, the power
supply should be an insulated type, and should be enclosed within a protective circuit. The
regulator on the unit is a non-insulated type.
If using a power supply device without an internal protective circuit, always make sure power
is supplied to the unit through a protective element such as a fuse.
4-10
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Brown: +24V
Allowable
Rated output
voltage range
20.4 to 28.8 V DC
At least 24 W
Power supply connector
Power supply cable (attached)
Green: Function earth
Blue: 0V
capacity