6.2 What to Do If an Error Occurs

6.2.1 ERROR LED Flashes on the CPU Unit

 Condition
A self-diagnostic error has occurred.
 Solution
Confirm the status in the following procedure.
PROCEDURE
1. Select "Online"  "Status Display" in FPWIN GR7, and check the error
details (error code).
2. Switch to the PROG. mode.
3. If a self-diagnosis error other than syntax error has occurred, cancel the
situation in accordance with the error code.
4. In the case of a syntax error, use the "Totally Check Project" function under
"Debug" in FPWIN GR7 to identify the syntax error.
KEY POINTS
In the case of an operation error, check the address where the error
occurred before performing error clearance.
In the case of an error coded 80 or higher, the error can be cleared by
pressing the [Error Clearance] button in the "Status Display" dialog box.
In the PROG. mode, the power supply can be turned off and then on again
to clear the error, but all of the contents of the operation memory except
hold type data are cleared.
An error can also be cleared by executing a self-diagnostic error set
instruction (ERR).