5. Select and double-click Slot No. 1.
The "Unit selection" dialog box is displayed.
6. In the unit type field, select a unit to be attached.
Subsequently, input words and output words are automatically entered.
7. As necessary, enter the starting word number and press the [OK] button.
The registered unit and the starting word number are included in the I/O map. A
number that combines the starting word number registered for each unit and 0 to
F becomes the starting I/O number.
6. Repeat registrations.
7. Press the [OK] button while the "FP7 configuration" dialog box is displayed.
KEY POINTS
The I/O map registered using FPWIN GR7 is downloaded into the CPU unit,
together with other project information. If a difference with the actual units
and/or attachment status is identified when power supply is turned on or
during operation, such a difference is reported as a self-diagnosis error.
If a starting word number is not entered, the system automatically enters
one.
Based on the starting word number allocated to each unit, I/O numbers are
allocated.
The starting number of I/O numbers allocated to the internal functions of
the CPU unit can be changed to another number from the word number 0.