Standard Menu - AuCom EMX3-1600C User Manual

Emx3 soft starter
Table of Contents

Advertisement

PROGRAMMING MENU
Application
Compressor Recip
Conveyor
Crusher Rotary
Crusher Jaw

10.5 Standard Menu

The standard menu provides access to commonly used parameters, allowing the user to configure the EMX3 as required for the
application. For details of individual parameters, refer to
Parameter Group
1
Motor Data-1
Motor Full Load Current
1A
2
Start/Stop Modes-1
Start Mode
2A
Start Ramp Time
2B
Initial Current
2C
Current Limit
2D
Stop Mode
2H
Stop Time
2I
3
Auto-Start/Stop
Auto-Start Type
3A
Auto-Start Time
3B
Auto-Stop Type
3C
Auto-Stop Time
3D
4
Protection Settings
Excess Start Time
4A
Undercurrent
4C
Undercurrent Delay
4D
Instantaneous Overcurrent
4E
Instantaneous Overcurrent Delay
4F
Phase Sequence
4G
40
| User Manual (710-04840-00M)
Parameter
Motor Full Load Current
Start Mode
Start Ramp Time
Current Limit
Motor Full Load Current
Start Mode
Start Ramp Time
Current Limit
Stop Mode
Adaptive Stop Profile
Stop Time
Motor Full Load Current
Start Mode
Start Ramp Time
Current Limit
Excess Start Time
Locked Rotor Time
Motor Full Load Current
Start Mode
Start Ramp Time
Current Limit
Excess Start Time
Locked Rotor Time
Parameter Descriptions
Suggested value
Model dependent
Constant Current
5 seconds
450%
Model dependent
Constant Current
5 seconds
400%
Adaptive Control
Constant Deceleration
10 seconds
Model dependent
Constant Current
10 seconds
400%
30 seconds
20 seconds
Model dependent
Constant Current
10 seconds
450%
40 seconds
30 seconds
on page 46.
Default Setting
Model dependent
Constant Current
10s
350%
350%
Coast To Stop
0s
Off
1m
Off
1m
20s
20%
5s
400%
0s
Any Sequence