Ul Short Circuit Ratings - AuCom EMX3-1600C User Manual

Emx3 soft starter
Table of Contents

Advertisement

POWER CIRCUITS
6.7

UL Short Circuit Ratings

Short circuit current ratings (SCCR) are available for 480 VAC and 600 VAC installations.
480 VAC circuits
For UL compliant installation, select a fuse that meets the specified fuse class and maximum fuse rating.
600 VAC circuits
For UL compliant installation, the starter can be protect by either fuses or a circuit breaker as specified in the following tables.
Fuse selection
@ 480 VAC max.
Model
Short
Circuit
Rating
EMX3-0023B
EMX3-0043B
EMX3-0050B
EMX3-0053B
EMX3-0076B
EMX3-0097B
EMX3-0100B
EMX3-0105B
EMX3-0145B
EMX3-0170B
65 kA
EMX3-0200B
EMX3-0220B
EMX3-0255B
EMX3-0350B
EMX3-0425B
EMX3-0500B
EMX3-0580B
EMX3-0700B
EMX3-0820B
EMX3-0920B
EMX3-1000B
EMX3-0255C
65 kA
EMX3-0360C
EMX3-0380C
EMX3-0430C
100 kA
EMX3-0620C
EMX3-0650C
EMX3-0790C
EMX3-0930C
EMX3-1200C
EMX3-1410C
65 kA
EMX3-1600C
XXX = blade type. Refer to Ferraz/Mersen catalog for details.
† - Models provided with a "3 cycle rating" are suitable for use in a circuit with the prospective current noted, when protected by any
UL Listed fuses or UL Listed circuit breakers sized according to the NEC.
20
| User Manual (710-04840-00M)
Max. Fuse
Short
Rating (A)
Circuit
Listed J, L or RK5 Class
(fuse class)
Rating
25 (J)
AJT25
50 (J)
AJT50
60 (J)
10 kA
AJT60
80 (J)
AJT80
100 (J)
AJT100
125 (J)
AJT125
150 (J)
AJT150 / RK5 200
175 (J)
AJT175 / RK5 200
200 (J)
18 kA
AJT200 / RK5 300
250 (J)
AJT250 / RK5 300
350 (RK1/J)
400 (J)
450 (J)
600 (J)
30 kA
Any 600 A, Class J
800 (L)
Any 800 A, Class L
42 kA
1200 (L)
Any 1200 A, Class L
85 kA
350 (RK1/J)
18 kA
AJT300
600 (L)
Any 600 A, Class L
800 (L)
100 kA
Any 800 A, Class L
1200 (L)
Any 1200 A, Class L
1600 (L)
A4BQ1600
2000 (L)
85 kA
A4BQ2000
A4BQ2500
@ 600 VAC
Ferraz/Mersen fuse,
Ferraz/Mersen fuse, R/C
Fuse
A070URD30XXX0063
A070URD30XXX0125
A070URD30XXX0200
A070URD30XXX0315
A070URD30XXX0450
Not available
A070URD33XXX0630
A070URD33XXX0700
Not available
A070URD33XXX1000
A070URD33XXX1400
A070URD30XXX0450
A070URD33XXX0630
A070URD33XXX0700
A070URD33XXX1000
A070URD33XXX1400
A065URD33XXX1800
A055URD33XXX2250
600 V Short cct
semi-conductor fuses
Not available
Not available
rating –
3 cycles †
18 kA –
For 3 cycles
30 kA –
For 3 cycles
42 kA –
For 3 cycles