Typical Examples of Poor Plumbing and Installation Practices
DO NOT:
Install the Digital Mixer Valve where it can become frozen
Install the Digital Mixer Valve where it can be subjected to ambient tempera-
tures in excess of 40ºC
Position the Digital Mixer Valve where maintenance access is poor or unsafe
Install into a system where the cold water cistern holds less than 230 litres
Install into a system where air locking could occur
Install the wireless controller in a position where communication with the
Digital Mixer Valve is poor e.g. mixer valve installed under metal bath, in front
of metal cistern, on foil backed plasterboard, more than the recommended
distance away etc.
Install the Digital Mixer Valve onto shared water supplies
Install the Digital Mixer Valve less than 100 mm from the lowest level of water
in the cistern (low pressure version only)
Fit plastic pipework unless rigidly supported
Install a High Pressure/Combi Valve to a Pumped Gravity System
Less than
230 Litres
Less than
230 Litres
Incorrect
Cold
Take-off
Incorrect
Hot
Take-off
Shared
Supplies
Plastic pipework
not rigidly
supported.
Incorrect
Hot
Take-off
Affected by Metal
Bath / Poor or no
Communication
Steel / Cast
No
Access
Air-locking
Pipework
Distance Too Far /
Poor or No
Communication
17
Bath Installation
Bath
Shower Installation
1144486-W2-K