Note On Connecting The 2 A Output Module - Siemens S7-1500 Manual

Simatic top connect
Hide thumbs Also See for S7-1500:
Table of Contents

Advertisement

5.3

Note on connecting the 2 A output module

Introduction
This section contains information on connecting the 2 A output module (2 amperes) with
SIMATIC TOP connect.
Connecting the supply voltage
Note
Before starting work, make sure you have read the wiring rules in Wiring rules (Page 21).
The potential supply must be at the front connector module, and a supplementary ground
connection to the terminal module is required for this purpose. To create this ground
connection, follow these steps.
1. Connect the supply voltage to each of the two potential clamps on the front connector
2. In addition to the connecting cable, connect one cable for M1 or M2 to each terminal
3. Connect M1 / M2 with a separate cable to the front connector module and terminal
SIMATIC TOP connect for S7-1500 and ET200MP
Manual,
module using separate cables.
module.
module.
The potential of M1 and M2 can be bridged.
2-ampere front connector module
Standard connecting cable between front connector module and terminal module
Additional connecting cable for M1 and M2
2 A output module
Wiring SIMATIC TOP connect to the I/O modules
5.3 Note on connecting the 2 A output module
41

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Et200mp

Table of Contents