Set the test criteria for the empty pipe condition. The factory default for this value is set to
five percent with limits configurable between one and ten percent. This parameter applies
to manually initiated test only.
Continuous limit
LOI menu path
Set the test criteria for the continuous SMART Meter Verification diagnostic. The factory
default for this value is set to five percent with limits configurable between two and ten
percent. If the tolerance band is set too tightly, under empty pipe conditions or noisy
flowing conditions, a false failure of the transmitter test may occur.
9.10

Run manual SMART Meter Verification

LOI menu path
The SMART Meter Verification diagnostic will be available if the advanced diagnostic suite
(DA2) was ordered. If DA2 was not ordered or licensed, this diagnostic will not be available.
This method will initiate the manual meter verification test.
9.10.1
Test conditions
LOI menu path
SMART Meter Verification can be initiated under three possible test conditions. This
parameter is set at the time that the sensor baseline or SMART Meter Verification test is
manually initiated.
No flow
Run the SMART Meter Verification test with a full pipe and no flow in the line. Running the
SMART Meter Verification test under this condition provides the most accurate results and
the best indication of magnetic flowmeter health.
Flowing full
Run the SMART Meter Verification test with a full pipe and flow in the line. Running the
SMART Meter Verification test under this condition provides the ability to verify the
magnetic flowmeter health without shutting down the process flow in applications when a
shutdown is not possible. Running the diagnostic under flowing conditions can cause a
false test failure if there is significant process noise present.
Reference manual
Diagnostics > Advanced Diag > Meter Verif > Test Criteria > Con-
tinual
Diagnostics > Advanced Diag > Meter Verif > Run Meter Ver
Diagnostics > Advanced Diag > Meter Verif > Run Meter Ver >
Test Condition
Advanced Diagnostics Configuration
123