Compute module environmental specifications
Specification
Temperature range*
Operating
Non-operating
Relative humidity (noncondensing)**
Operating
Non-operating
Altitude†
Operating
Non-operating
* The following temperature conditions and limitations apply:
•
All temperature ratings shown are for sea level.
•
An altitude derating of 1°C per 305m (1.8°F per 1,000.7 ft) above sea level
•
No direct sunlight is allowed.
•
The maximum permissible rate of change is 10°C/hr (18°F/hr).
•
The type and number of options installed might reduce the upper temperature and humidity limits.
•
Operating with a fan fault or above 30°C (86°F) might reduce system performance.
** Storage maximum humidity of 95% is based on a maximum temperature of 45°C (113°F).
† Maximum storage altitude corresponds to a minimum pressure of 70 kPa (10.1 psia).
Compute module physical specifications
The following details physical specifications for the HPE Synergy 480 Gen10 compute module.
Specification
Height
Depth
Width
Weight (maximum)
Weight (minimum)
76
Specifications
Value
—
10°C to 35°C (50°F to 95°F)
-30°C to 60°C (-22°F to 140°F)
—
8% to 90% @ -12°C - 24°C (10.4°F - 75.2°F)
5% to 95% relative humidity (Rh) @ 38.7°C
(101.7°F), maximum wet bulb temperature, non-
condensing
—
3050 m (10,000 ft)
9144 m (30,000 ft)
Value
63.60 mm (2.50 in)
606.50 mm (23.88 in)
214.00 mm (8.43 in)
8.16 kg (18.00 lb)
6.57 kg (14.50 lb)