Configure and Program the Controller
If you want to
Synchronize the secondary
controller
Set the clock of the SRM
module
Publication 1756-UM523F-EN-P - December 2006
Configuring a Message to an SRM (Continued)
On this tab
For this item
Configuration
Message Type
Service Code
Class name
Instance name
Attribute name
Source
Num. Of Elements
Destination
Communication
Path
Connected check box.
Configuration
Message Type
Service Code
Class name
Instance name
Attribute name
Source
Num. Of Elements
Destination
Communication
Path
Connected check box
Type or select
CIP Generic
4c
bf
1
Leave blank
INT tag with a value of 1
2
Leave blank
1, slot_number
where:
slot_number is the left-hand slot number of the
1757-SRM module.
Leave the Connected check box clear (unchecked). You can
send only unconnected messages to a 1757-SRM module.
CIP Generic
10
8b
1
1
WallClockTime[0]
where:
WallClockTime is a DINT[2] array that stores the
CurrentValue of the WALLCLOCKTIME object.
8
Leave blank
1, slot_number
where:
slot_number is the left-hand slot number of the
1757-SRM module.
Leave the Connected check box clear (unchecked). You can
send only unconnected messages to a 1757-SRM module.