Parameter
EtherNet/IP Network
ControlNet Network
Operator Interface Terminals
Operator Interfaces
PanelView Standard terminal
• PanelView Plus terminal
• VersaView industrial computer running a
Windows CE operating system
RSView Supervisory Edition software with
RSLinx Enterprise software
• RSView Supervisory Edition software with
RSLinx 2.x software
• RSView 32 software
• Any other HMI client software that uses
RSLinx 2.x software
• PanelView Standard terminal
• PanelView 1000e/1400e terminal
• PanelView Plus terminal
• VersaView industrial computer running a
Windows CE operating system
• RSView Supervisory Edition software with
RSLinx 2.x software
• RSView 32 software
• Any other HMI client software that uses
RSLinx 2.x software
ControlLogix Redundancy System Overview
Criteria
Same as a nonredundant system
• Use RSLinx Enterprise software revision
3.0 or later.
• Set aside connections for each PanelView
Plus or VersaView CE terminal:
In this module
controller
ENBT
EWEB
• Use RSLinx Enterprise software revision
3.0 or later.
• Use IP swapping.
• Keep the HMI and both redundant chassis
on the same subnet.
Limit the number of RSLinx servers that a
controller uses to 1 (ideal) to 3 (maximum).
Do terminals use unscheduled
communication?
• Yes — Use ≤ 4 terminals per controller.
• No — Use the number of terminals that
you need.
• Use RSLinx Enterprise software revision
3.0 or later.
• Set aside connections for each PanelView
Plus or VersaView CE terminal.
In this module
Set aside
Controller
5 connections
CNB
5 connections
Limit the number of RSLinx servers that a
controller uses to 1 (ideal) to 3 (maximum).
Publication 1756-UM523F-EN-P - December 2006
Page
28, 32, 38
Set aside
5 connections
5 connections
5 connections
28, 32, 35
25