Allen-Bradley 1756-CNB User Manual page 140

Controllogix redundancy system
Hide thumbs Also See for 1756-CNB:
Table of Contents

Advertisement

140
Update Modules and Redundant Systems
Action
1. Update the software.
2. Add the latest EDS files.
3. Put the keyswitches in the REM position.
4. Open the SRM configuration tool for the
primary chassis.
Publication 1756-UM523F-EN-P - December 2006
Details
A. Go to the tool tray of your computer and shutdown RSLinx software.
B. Update this software:
• 1757-SRM System Redundancy Module Configuration tool
• RSLogix 5000 software
• RSLinx software
• RSNetWorx software
• ControlFLASH firmware update kit.
If you are planning to uninstall version 13 of your RSLogix 5000 software, wait until you
have completed and validated your update.
Start ⇒ Programs ⇒ Rockwell Software ⇒ RSLinx Tools ⇒ EDS Hardware Installation
Tool
Put the keyswitch of each redundant controller to the REM position. Otherwise you will not
be able to update the system.
A. Start RSLinx software.
B. From the Communications menu, choose RSWho.
C. Open the branches of your network until you find the 1757-SRM module in the primary
chassis.
D. Right-click the SRM and choose Module Configuration.