3. Preparation

3.1. Installation

3.1
Installation
Refer to the XYR 6000 Transmitter Quick Start Guide (document 34-XY-25-21) for installation, mounting
and wiring of your XYR 6000 transmitter.
3.2

Configuration

The XYR 6000 Transmitter contains the electronics interface compatible for connecting to the
OneWireless network. An operator uses the Wireless Builder application to configure blocks, to change
operating parameters, and to create linkages between blocks that make up the transmitter's configuration.
These changes are written to the transmitter when it is authenticated by a security key.
3.3

Connecting to network

Use Authentication Device to connect your transmitter to the OneWireless network. See page 24.
3.4

Calibrating the transmitter

Methods

The following calibration methods are available through the transmitter menu.
User Calibration - Calibrates the channel to the low and high range values for selected input type.
Restore Calibration - constants for the channel 1 are restored to factory defaults.
Clear Calibration - FACTORY or USER Calibration constants for the channel can be cleared.

Wireless Builder

Wireless Builder must be used to unlock and take the channel to be calibrated out of service. Calibration
Point High (CAL_PT_HI), Calibration Point Low (CAL_PT_LO) & Cal Unit (CAL_UNIT) can be set
from Wireless Builder.
PV value is scaled to Engineering Units. For example, for 1-5V input type if EU 0 = 0 and EU 100 = 100
then Input (1-5V) will be scaled to 0 to 100.
Calibration points CAL_LO and CAL_HI are considered in terms of engineering units. For example,
If channel is to be calibrated for (1-3V) with above settings then set CAL_PT_LO to 0 and
CAL_PT_HI to 50.
If channel is to be calibrated for (1-4V) with above settings then set CAL_PT_LO to 0 and
CAL_PT_HI to 75. Calibration unit has no significance.